1、常用的電線(xian)、電纜(lan)按(an)用途分有(you)哪些(xie)種類?
答(da):按用(yong)途可分為裸導線、絕緣電(dian)(dian)線、耐熱電(dian)(dian)線、屏蔽電(dian)(dian)線、電(dian)(dian)力電(dian)(dian)纜、控制電(dian)(dian)纜、通信電(dian)(dian)纜、射(she)頻電(dian)(dian)纜等。
2、絕(jue)緣(yuan)電線有(you)哪幾(ji)種?
答:常有的(de)絕(jue)(jue)緣電(dian)線(xian)(xian)(xian)(xian)有以下幾(ji)種:聚(ju)氯乙(yi)(yi)烯(xi)(xi)絕(jue)(jue)緣電(dian)線(xian)(xian)(xian)(xian)、聚(ju)氯乙(yi)(yi)烯(xi)(xi)絕(jue)(jue)緣軟(ruan)(ruan)線(xian)(xian)(xian)(xian)、丁腈聚(ju)氯乙(yi)(yi)烯(xi)(xi)混(hun)合物(wu)絕(jue)(jue)緣軟(ruan)(ruan)線(xian)(xian)(xian)(xian)、橡皮絕(jue)(jue)緣電(dian)線(xian)(xian)(xian)(xian)、農用(yong)地下直埋鋁(lv)芯塑(su)料絕(jue)(jue)緣電(dian)線(xian)(xian)(xian)(xian)、橡皮絕(jue)(jue)緣棉紗紡織(zhi)軟(ruan)(ruan)線(xian)(xian)(xian)(xian)、聚(ju)氯乙(yi)(yi)烯(xi)(xi)絕(jue)(jue)緣尼龍(long)護套電(dian)線(xian)(xian)(xian)(xian)、電(dian)力和照(zhao)明用(yong)聚(ju)氯乙(yi)(yi)烯(xi)(xi)絕(jue)(jue)緣軟(ruan)(ruan)線(xian)(xian)(xian)(xian)等(deng)。
3、電(dian)纜橋架適合(he)于何種場(chang)合(he)?
答:電纜(lan)橋架(jia)適用(yong)于一(yi)般工礦企業室內外架(jia)空敷(fu)設電力電纜(lan)、控制(zhi)電纜(lan),亦可用(yong)于電信、廣(guang)播電視等部門在(zai)室內外架(jia)設。
4、電纜附件有哪(na)些(xie)?
答(da):常(chang)用(yong)的電附件有(you)電纜(lan)終端接線(xian)盒、電纜(lan)中間接線(xian)盒、連(lian)接管及接線(xian)端子、鋼板接線(xian)槽、電纜(lan)橋架等。
5、什么叫(jiao)電(dian)纜中間接頭?
答:連接電纜與(yu)電纜的導體(ti)、絕(jue)緣(yuan)屏蔽層(ceng)和保護(hu)層(ceng),以(yi)使電纜線路連接的裝置(zhi),稱為電纜中間接頭。
6、什(shen)么叫電(dian)氣主接線?
答(da):電(dian)氣(qi)主接線是(shi)發電(dian)廠(chang)、變電(dian)所(suo)中主要電(dian)氣(qi)設備和(he)母線的(de)連接方(fang)式,包括主母線和(he)廠(chang)用電(dian)系(xi)統(tong)按一定的(de)功能要求的(de)連接方(fang)式。
7、在選擇電力電纜的截面時,應遵照哪些規定(ding)?
答(da):電(dian)(dian)(dian)力電(dian)(dian)(dian)纜的(de)選擇應(ying)遵照以下原則:(1)電(dian)(dian)(dian)纜的(de)額(e)定(ding)電(dian)(dian)(dian)壓要大于或等于安裝(zhuang)點(dian)供(gong)(gong)電(dian)(dian)(dian)系(xi)統的(de)額(e)定(ding)電(dian)(dian)(dian)壓;(2)電(dian)(dian)(dian)纜持(chi)續(xu)(xu)容(rong)許電(dian)(dian)(dian)流應(ying)等于或大于供(gong)(gong)電(dian)(dian)(dian)負載(zai)的(de)更大 持(chi)續(xu)(xu)電(dian)(dian)(dian)流;(3)線芯截面要滿足供(gong)(gong)電(dian)(dian)(dian)系(xi)統短(duan)路(lu)時的(de)穩定(ding)性(xing)的(de)要求;(4)根據(ju)電(dian)(dian)(dian)纜長度驗算電(dian)(dian)(dian)壓降是否符合要求;(5)線路(lu)末端的(de)最小(xiao)短(duan)路(lu)電(dian)(dian)(dian)流應(ying)能(neng)使(shi)保護裝(zhuang)置可靠的(de)動作。
8、交聯聚(ju)乙烯電纜(lan)和油紙(zhi)電纜(lan)比較有哪些優(you)點?
答:(1)易安(an)裝,因為(wei)(wei)它允許最小彎曲半徑小、且重量(liang)輕;(2)不受線路(lu)落差*;(3)熱性能好,允許工作(zuo)溫度高(gao)、傳(chuan)輸容量(liang)大(da);(4)電纜附(fu)件簡(jian)(jian)單(dan),均為(wei)(wei)干式結構;(5)運行(xing)維護簡(jian)(jian)單(dan),無漏油問題;(6)價(jia)格較(jiao)低;(7)可靠性高(gao)、故障(zhang)率低;(8)制造工序少、工藝(yi)簡(jian)(jian)單(dan),經濟效益顯(xian)著(zhu)。
9、固定(ding)交流單芯電纜的夾具有什么要求?為(wei)什么?
答:夾具應無(wu)鐵件(jian)構成閉合磁(ci)路,這是因為當電(dian)纜(lan)(lan)(lan)線(xian)(xian)芯通(tong)過電(dian)流時(shi),在其周(zhou)圍產(chan)生磁(ci)力(li)線(xian)(xian),磁(ci)力(li)線(xian)(xian)與通(tong)過線(xian)(xian)芯的(de)電(dian)流大小成正比,若使(shi)(shi)用(yong)鐵件(jian)等導磁(ci)材料(liao),根據電(dian)磁(ci)感應可知,將(jiang)在鐵件(jian)中(zhong)產(chan)生渦流使(shi)(shi)電(dian)纜(lan)(lan)(lan)發熱,甚至燒壞電(dian)纜(lan)(lan)(lan)。所以不(bu)可使(shi)(shi)用(yong)鐵件(jian)作單芯交流電(dian)纜(lan)(lan)(lan)的(de)固(gu)定(ding)夾具。
10、以下的熱縮電(dian)纜頭(tou)的附件的更大(da) 特(te)點和優點是什么?
答(da):熱(re)縮附(fu)件的(de)(de)更大 特點是用應(ying)力(li)管代替傳(chuan)統的(de)(de)應(ying)力(li)錐(zhui),它不僅(jin)簡(jian)化了(le)(le)施工(gong)工(gong)藝,還縮小了(le)(le)接(jie)頭的(de)(de)終端的(de)(de)尺(chi)寸(cun),安裝方便,省時省工(gong),性能優(you)越,節約金屬。熱(re)縮電纜(lan)附(fu)件集灌(guan)注式(shi)和干包(bao)式(shi)為(wei)一體,集合了(le)(le)這(zhe)兩種(zhong)附(fu)件的(de)(de)優(you)點。
11、電纜(lan)敷設(she)前應進行哪些(xie)檢(jian)查工作?
答:(1)支架(jia)應(ying)齊全、油漆完整。(2)電(dian)纜(lan)(lan)(lan)型號、電(dian)壓、規格符合(he)設計。(3)電(dian)纜(lan)(lan)(lan)絕緣(yuan)良好,當(dang)對(dui)油紙電(dian)纜(lan)(lan)(lan)的密封(feng)有(you)懷疑時,應(ying)進(jin)行受潮判(pan)斷;直(zhi)埋電(dian)纜(lan)(lan)(lan)與小底電(dian)纜(lan)(lan)(lan)應(ying)經(jing)直(zhi)流(liu)耐(nai)壓試難合(he)格;充(chong)油電(dian)纜(lan)(lan)(lan)的油樣(yang)應(ying)試驗合(he)格。(4)充(chong)油電(dian)纜(lan)(lan)(lan)的油壓不宜低(di)于1.47MPa。
11、交(jiao)聯熱收(shou)縮電纜(lan)附件有哪些(xie)優點?
答:這是一(yi)種新型材料,它與(yu)現在其他類型附件比較具有電氣性能優越、體(ti)積(ji)小(xiao)、質量小(xiao)、安裝簡便(bian)、材料配(pei)套等優點,另外還具有耐氣候、抗污穢(hui)性、阻燃自(zi)熄(xi)等能力。
12、對油紙(zhi)絕緣電(dian)力電(dian)纜(lan)密封有懷疑時,如何用較簡單的辦法檢查電(dian)纜(lan)絕緣紙(zhi)是否受潮?
答:把電纜(lan)絕緣紙點燃或放(fang)入150℃左右的電纜(lan)油中檢查,無“嘶嘶”聲(sheng)或白色(se)泡沫(mo)出現,說明未受(shou)潮。
13、電纜標志牌應注明什么內容(rong)?編(bian)寫有何要求?
答:標(biao)志牌(pai)上應注明電纜(lan)線路設計編號(hao)、電纜(lan)型號(hao)、規格及始點,并聯使用的電纜(lan)應有順序號(hao)。要求字跡清晰、不易(yi)脫(tuo)落。
14、直埋電纜的方位(wei)標志應(ying)設置在哪些位(wei)置?
答:在電(dian)纜(lan)兩端,電(dian)纜(lan)直線段50~100m處電(dian)纜(lan)接頭幾電(dian)纜(lan)改變方向的彎角處。
15、制作電纜接頭(tou)用的黃臘綢(chou)帶(dai)(dai)、黑(hei)玻璃(li)漆帶(dai)(dai)、無(wu)堿玻璃(li)絲帶(dai)(dai)等,施(shi)工前如何進行(xing)排潮(chao)處理?
答:(1)恒溫干(gan)燥(zao)法(fa):將絕緣帶卷(juan)(juan)成(cheng)直徑為(wei)25~30mm小卷(juan)(juan),放入(ru)110~120℃恒溫干(gan)燥(zao)箱內(nei)烘(hong)4~5h,冷(leng)卻(que)干(gan)取出,放入(ru)干(gan)燥(zao)的(de)密(mi)封(feng)筒內(nei)。(2)油(you)(you)浸(jin)排潮法(fa):將絕緣帶小卷(juan)(juan)放入(ru)恒溫在120~130℃的(de)電纜油(you)(you)中(zhong),離鍋(guo)底保(bao)持30mm距離,經一定時間后油(you)(you)面不再(zai)產生泡沫后取出,裝入(ru)貯(zhu)有電纜油(you)(you)的(de)桶中(zhong),油(you)(you)位應超過所(suo)有裝入(ru)的(de)物(wu)體并將其密(mi)封(feng)。
16、電纜外護層的(de)作用是什(shen)么?
答(da):保(bao)護(hu)內護(hu)層不受機(ji)械(xie)損傷和化(hua)學(xue)腐蝕(shi),增強機(ji)械(xie)強度。
17、室外電纜溝應符合哪些要求(qiu)?
答(da):電纜溝上部(bu)應比(bi)地面稍(shao)高,加蓋用混凝土制(zhi)作的(de)蓋板,電纜應平敷(fu)在支架上,有良好(hao)的(de)排(pai)水管。
18、電纜內護層的作用是什么?
答(da);使(shi)絕緣(yuan)層(ceng)不會與水、空氣或(huo)其(qi)他物體接觸,防止絕緣(yuan)受潮(chao)和絕緣(yuan)層(ceng)不受機械傷(shang)害。
19、使用鋼絲鉗時應注意些什(shen)么?
答:使用(yong)前,一定要檢查絕(jue)緣柄的絕(jue)緣是否完好無損(sun),使用(yong)時不可用(yong)鋼(gang)絲鉗(qian)剪切(qie)超過規格所允許的金屬線(xian)材,并禁止用(yong)鋼(gang)絲鉗(qian)代替錘子(zi)敲打工具(ju),以免(mian)損(sun)壞。
20、什(shen)么(me)叫絕緣強(qiang)度?
答:絕(jue)緣物(wu)質在(zai)電(dian)場中(zhong),當電(dian)場強度(du)增大到(dao)某一極限(xian)時就會被擊(ji)穿(chuan),這(zhe)個(ge)導(dao)致絕(jue)緣擊(ji)穿(chuan)的電(dian)場強度(du)稱為絕(jue)緣強度(du)。
22、對電纜導體連接點(dian)的(de)機(ji)械強(qiang)度(du)有何要求?
答:連接(jie)點的機械強度(du)(du),一般低于電纜(lan)導體本(ben)身的抗拉(la)強度(du)(du),對于固定(ding)敷設的電力電纜(lan),其(qi)連接(jie)點的抗拉(la)強度(du)(du)要(yao)求(qiu)不低于導體本(ben)身抗拉(la)強度(du)(du)的60%。
23、電力電纜的絕緣層材(cai)料應具備(bei)哪些(xie)主要(yao)性(xing)能?
答;應具(ju)備下列主要性(xing)能:(1)高(gao)(gao)的(de)(de)擊穿強度;(2)低的(de)(de)介(jie)質損耗(hao);(3)相當高(gao)(gao)的(de)(de)絕緣電阻;(4)優良的(de)(de)耐放電性(xing)能;(5)具(ju)有一定的(de)(de)柔(rou)軟性(xing)和機械強度;(6)絕緣性(xing)能長期穩定。
24、機(ji)械敷設(she)電纜時,牽引(yin)強度有(you)何規定?
答(da):對于銅芯電(dian)纜(lan),當牽(qian)引(yin)頭部時(shi),允許牽(qian)引(yin)強(qiang)度(du)為(wei)70N/cm;對于鋁芯電(dian)纜(lan),當牽(qian)引(yin)頭部時(shi),允許牽(qian)引(yin)強(qiang)度(du)為(wei)40N/cm;若利用(yong)鋼絲網(wang)套牽(qian)引(yin)時(shi),鉛護套電(dian)纜(lan)允許強(qiang)度(du)為(wei)10N/cm;鉛護套電(dian)纜(lan)為(wei)40N/cm。
25、對電(dian)纜保護管有何規(gui)定?
答:(1)電纜需要穿(chuan)保護管(guan)(guan)敷設時,管(guan)(guan)子內(nei)徑不(bu)應(ying)小于(yu)(yu)電纜外徑的(de)1.5倍(bei),混凝土(tu)管(guan)(guan)、陶土(tu)管(guan)(guan)、石(shi)棉、水泥管(guan)(guan)的(de)內(nei)徑不(bu)應(ying)小于(yu)(yu)100mm;
(2)電(dian)纜管(guan)的(de)彎曲半(ban)徑(jing)應符合(he)所穿入電(dian)纜彎曲半(ban)徑(jing)的(de)規定;
(3)每根管(guan)子最(zui)多不應(ying)超過三(san)個彎(wan)頭,直角彎(wan)不應(ying)多于(yu)2個。
26、如何(he)測量(liang)電(dian)纜護套(tao)的(de)外(wai)徑?
答(da):在(zai)護(hu)套圓周上均(jun)勻分(fen)布(bu)的五點處,測量(liang)護(hu)套外(wai)徑(jing)和其平均(jun)值(zhi),其平均(jun)外(wai)徑(jing)既(ji)為護(hu)套的外(wai)徑(jing)。
27、不同截面的(de)銅芯(xin)電纜如何(he)連接?
答:不同截面(mian)的(de)銅(tong)(tong)芯電纜連(lian)接(jie),可采(cai)用開口弱背銅(tong)(tong)接(jie)管(guan),以(yi)錫焊法連(lian)接(jie),也可用純銅(tong)(tong)棒(bang)按不同的(de)截面(mian)要求連(lian)接(jie)成銅(tong)(tong)接(jie)管(guan),以(yi)壓接(jie)法連(lian)接(jie)。
28、簡(jian)述(shu)10KV交聯電纜(lan)熱縮式(shi)制作戶內終端頭的(de)過(guo)程?
答;(1)準備階段:檢(jian)(jian)(jian)查熱縮電(dian)纜(lan)(lan)附(fu)件是(shi)否齊(qi)備,型號是(shi)否相配,檢(jian)(jian)(jian)查并(bing)確認電(dian)纜(lan)(lan)有無潮氣(qi)后,檢(jian)(jian)(jian)查電(dian)纜(lan)(lan)。
(2)切除(chu)多(duo)余(yu)電(dian)纜(lan),根(gen)據(ju)現場情況決(jue)定(ding)電(dian)纜(lan)長度。
(3)剝除護層。
(4)焊(han)接(jie)接(jie)地線,將接(jie)地線焊(han)接(jie)在(zai)鋼帶(dai)上。
(5)填(tian)充三叉(cha)口及繞包(bao)密封膠。
(6)安裝三芯(xin)分支護套(tao),將護套(tao)套(tao)入根部(bu),從中部(bu)開始收縮,先(xian)往(wang)根部(bu),再往(wang)指部(bu)。
(7)剝(bo)銅(tong) 帶(dai)和外半導電(dian)層,剝(bo)切三芯(xin)分支套口20mm以上的銅(tong)帶(dai),嚴禁損(sun)傷主絕(jue)緣,清(qing)除干凈半導電(dian)層。
(8)安裝應力管,管口端(duan)部分支(zhi)套對接后(hou)熱縮。
(9)安裝接線端子。
(10)安(an)裝絕緣(yuan)管。
(11)安裝(zhuang)密(mi)封管。
(12)核相后安裝相色管。
29、戶內、戶外預制(zhi)式終端安裝步驟(zou)有哪些?
答:(1) 將電纜(lan)按預定位置就位、固定、清(qing)潔表面,參照說明書剝除外(wai)護套,如有特殊需要,外(wai)護套剝切長(chang)度可調整(zheng),分別由銅帶、外(wai)護套鎧裝引出2組(zu)地線。
(2) 由外(wai)護套口向上(shang)量(liang)取需要尺(chi)寸,切(qie)除多余電纜,套入熱(re)縮三(san)(san)指套至三(san)(san)叉口根部(bu)由中間加熱(re)收縮,由指套上(shang)口向上(shang)量(liang)取規定尺(chi)寸(35kv為(wei)350~380mm)。去掉多余銅帶(保留(liu)20mm),再保留(liu)半導體(ti)預定位置,壓接出線端子密(mi)封。
30、電線電纜的應(ying)用主要分為三(san)大類 :
(1)、電力系(xi)統
電(dian)(dian)力系(xi)統采用的電(dian)(dian)線(xian)(xian)電(dian)(dian)纜產品主要有(you)架(jia)(jia)空裸電(dian)(dian)線(xian)(xian)、匯流排(母(mu)線(xian)(xian))、電(dian)(dian)力電(dian)(dian)纜(塑(su)料(liao)線(xian)(xian)纜、油紙力纜(基本(ben)被塑(su)料(liao)電(dian)(dian)力電(dian)(dian)纜代(dai)替)、橡(xiang)套線(xian)(xian)纜、架(jia)(jia)空絕緣電(dian)(dian)纜)、分支電(dian)(dian)纜(取代(dai)部分母(mu)線(xian)(xian))、電(dian)(dian)磁線(xian)(xian)以(yi)及電(dian)(dian)力設備用電(dian)(dian)氣裝(zhuang)備電(dian)(dian)線(xian)(xian)電(dian)(dian)纜等。
(2)、信(xin)息傳(chuan)輸系(xi)統
用于信息傳輸系統的電(dian)(dian)(dian)(dian)線電(dian)(dian)(dian)(dian)纜(lan)(lan)主(zhu)要有(you)市話(hua)電(dian)(dian)(dian)(dian)纜(lan)(lan)、電(dian)(dian)(dian)(dian)視(shi)電(dian)(dian)(dian)(dian)纜(lan)(lan)、電(dian)(dian)(dian)(dian)子線纜(lan)(lan)、射頻電(dian)(dian)(dian)(dian)纜(lan)(lan)、光纖纜(lan)(lan)、數據電(dian)(dian)(dian)(dian)纜(lan)(lan)、電(dian)(dian)(dian)(dian)磁線、電(dian)(dian)(dian)(dian)力通(tong)訊或其他復合電(dian)(dian)(dian)(dian)纜(lan)(lan)等。
(3)、機械設(she)備、儀器儀表系(xi)統
此部分除(chu)架空裸電(dian)線(xian)外幾乎其他所(suo)有產品(pin)均有應用,但主(zhu)要(yao)是(shi)電(dian)力電(dian)纜(lan)、電(dian)磁線(xian)、數(shu)據(ju)電(dian)纜(lan)、儀器儀表(biao)線(xian)纜(lan)等。
31、電線電纜產(chan)品主要分為五大類:
(1)、裸電線(xian)及裸導(dao)(dao)體制品 本類產(chan)品的主(zhu)(zhu)要(yao)(yao)特征是:純的導(dao)(dao)體金屬,無絕緣及護套層,如(ru)鋼芯(xin)鋁絞(jiao)線(xian)、銅鋁匯流排、電力(li)機(ji)車線(xian)等;加工(gong)(gong)工(gong)(gong)藝(yi)主(zhu)(zhu)要(yao)(yao)是壓力(li)加工(gong)(gong),如(ru)熔煉、壓延、拉制、絞(jiao)合/緊壓絞(jiao)合等;產(chan)品主(zhu)(zhu)要(yao)(yao)用在(zai)城郊(jiao)、農村、用戶主(zhu)(zhu)線(xian)、開(kai)關柜等。
(2)、電(dian)(dian)(dian)力電(dian)(dian)(dian)纜本類產品主(zhu)要特征是:在導(dao)體外擠(繞(rao))包絕(jue)緣層,如(ru)架空絕(jue)緣電(dian)(dian)(dian)纜,或(huo)幾芯絞合(對應電(dian)(dian)(dian)力系(xi)統的(de)相線、零線和地線),如(ru)二芯以上架空絕(jue)緣電(dian)(dian)(dian)纜,或(huo)再增加護(hu)套層,如(ru)塑(su)料/橡套電(dian)(dian)(dian)線電(dian)(dian)(dian)纜。主(zhu)要的(de)工(gong)藝技(ji)術有拉制、絞合、絕(jue)緣擠出(繞(rao)包)、成纜、鎧裝、護(hu)層擠出等,各種產品的(de)不同(tong)工(gong)序組(zu)合有一(yi)定(ding)區別。
產品主要用(yong)在發、配、輸(shu)、變、供(gong)電(dian)線路中(zhong)的強電(dian)電(dian)能傳輸(shu),通(tong)過的電(dian)流大(幾十安(an)至幾千(qian)安(an))、電(dian)壓(ya)高(220V至500kV及(ji)以上)。
(3)、電氣裝備用(yong)電線(xian)(xian)電纜該類產品(pin)主(zhu)要特征是:品(pin)種規格繁(fan)多,應用(yong)范圍廣泛,使用(yong)電壓在1kV及以下較多,面對特殊場合(he)不斷衍生新的產品(pin),如耐火(huo)線(xian)(xian)纜、阻燃(ran)線(xian)(xian)纜、低(di)(di)煙無鹵/低(di)(di)煙低(di)(di)鹵線(xian)(xian)纜、防白蟻(yi)、防老(lao)鼠線(xian)(xian)纜、耐油/耐寒(han)/耐溫/耐磨線(xian)(xian)纜、醫(yi)用(yong)/農用(yong)/礦用(yong)線(xian)(xian)纜、薄(bo)壁電線(xian)(xian)等(deng)。
(4)、通訊電(dian)纜(lan)(lan)(lan)及光(guang)纖(簡略介紹)隨著近二十(shi)多年來,通訊行業的(de)飛速發(fa)展,產品也有(you)驚(jing)人的(de)發(fa)展速度。從過去(qu)的(de)簡單的(de)電(dian)話電(dian)報線纜(lan)(lan)(lan)發(fa)展到幾千(qian)對的(de)話纜(lan)(lan)(lan)、同軸纜(lan)(lan)(lan)、光(guang)纜(lan)(lan)(lan)、數據電(dian)纜(lan)(lan)(lan),甚至組合通訊纜(lan)(lan)(lan)等。
該類產品結構(gou)尺寸通常較小而均勻,制造精度要求高。
(5)、電磁線(繞組(zu)線)主要(yao)用于(yu)各(ge)種電機、儀(yi)(yi)器儀(yi)(yi)表等(deng)。
電線電纜的衍生(sheng)/新產品(pin)
電線電纜的衍生/新產(chan)品主要(yao)(yao)是因應(ying)用場合、應(ying)用要(yao)(yao)求(qiu)不同(tong)及裝(zhuang)(zhuang)備(bei)的方便性和降低裝(zhuang)(zhuang)備(bei)成本(ben)等的要(yao)(yao)求(qiu),而采用新材料、特(te)殊(shu)材料、或改變產(chan)品結(jie)構、或提高工(gong)藝(yi)要(yao)(yao)求(qiu)、或將不同(tong)品種的產(chan)品進行組合而產(chan)生。
采(cai)用不同材料(liao)如(ru)阻燃線纜(lan)、低(di)煙(yan)無(wu)鹵/低(di)煙(yan)低(di)鹵線纜(lan)、防白蟻、防老(lao)鼠(shu)線纜(lan)、耐(nai)油(you)/耐(nai)寒(han)/耐(nai)溫線纜(lan)等(deng);
改變產品結構如:耐(nai)火電纜等(deng);
提(ti)高工藝要求如:醫(yi)用線纜(lan)等(deng);
組合(he)產(chan)品如(ru):OPGW等;
方(fang)便(bian)安裝和降低裝備(bei)成本如:預(yu)制分支電纜等。
32、母(mu)線裝置施工完,應進行哪些檢查?
答:應進(jin)行下列檢查:
(1)金(jin)屬構(gou)件的加工、配制、焊接螺(luo)接應符合(he)規定;
(2)各部(bu)螺栓、墊圈、開口銷等零(ling)部(bu)件應齊全可靠(kao);
(3)母線配制及安(an)裝架應符(fu)合規定,相間及對地電氣距離符(fu)合要求;
(4)瓷件、鐵件及膠合處(chu)應完整(zheng),充(chong)油套管(guan)應無滲油,油位正常;
(5)油漆完整,相色正確,接地良好。
33、在(zai)35kv及(ji)以下電(dian)力電(dian)纜接頭中,改善其(qi)護(hu)套斷(duan)開處電(dian)場分布(bu)的方法有幾(ji)種(請(qing)列(lie)出五種),并簡(jian)述其(qi)方法。
答:(1)脹喇叭口:在(zai)鉛(qian)包割斷處把鉛(qian)包邊緣撬(qiao)起,成喇叭狀,其(qi)邊緣應光滑、圓(yuan)整、對稱。
(2)預(yu)留統包絕緣(yuan):在鉛包切口至電纜芯線分開點之(zhi)間(jian)留有一(yi)段統包絕緣(yuan)紙。
(3)切除(chu)半(ban)導(dao)電紙:將半(ban)導(dao)電紙切除(chu)到喇叭口以下。
(4)包繞應(ying)力錐:用(yong)絕(jue)緣包帶和(he)導電金(jin)屬材(cai)料包成錐形,人(ren)為地將屏蔽(bi)層擴大(da),以(yi)改(gai)善電場分布。
(5)等電(dian)位法:對于(yu)干包型或交聯聚乙烯電(dian)纜頭,在(zai)各線芯概況絕緣表面上包一段金屬帶(dai),并將其連接在(zai)一起(qi)。
(6)裝設應力(li)控制管:對于35kv及發(fa)下熱縮(suo)管電纜(lan)頭,首(shou)先從線芯銅(tong)屏蔽層(ceng)末(mo)端(duan)方向經半導體帶至線芯絕緣概況包繞(rao)2層(ceng)半導體帶,然(ran)后將相(xiang)應規格折(zhe)應力(li)管,套在銅(tong)屏蔽的末(mo)端(duan)處(chu),熱縮(suo)成形(xing)。
34、電纜支架(jia)的加工應符合(he)哪些要求(qiu)?
答:(1)鋼材(cai)應平(ping)直,無明顯扭曲,下料誤差應在5mm范圍內(nei),切口應無卷邊,毛(mao)剌;
(2)支架應焊接牢固,無(wu)顯(xian)蓍變形,各橫撐間的垂直凈距(ju)與設計偏差(cha)不應大于5mm;
(3)金屬支架必須進(jin)行(xing)防(fang)腐(fu)處(chu)理,位于濕熱、鹽(yan)、霧以及有化學腐(fu)蝕地(di)區時,應根據設計作特殊的防(fang)腐(fu)處(chu)理。
35、列舉出你熟悉的電纜架。
答:拼焊式(shi)E型架(jia)、裝(zhuang)配式(shi)E型架(jia)、橋式(shi)電纜(lan)架(jia)、電纜(lan)托(tuo)架(jia)、掛鉤式(shi)支(zhi)架(jia)、單根電纜(lan)支(zhi)架(jia)等。
36、敷設電纜應(ying)滿足哪些要求?
答:應(ying)滿足以下要求:
(1)安(an)全運(yun)行方(fang)面,盡可(ke)能(neng)避免各種(zhong)外(wai)來損壞,提高電纜(lan)線(xian)路的(de)供電可(ke)靠性;
(2)經濟方面(mian),從投資最省(sheng)的方面(mian)考慮(lv);
(3)施工方面,電(dian)纜(lan)線(xian)路的(de)(de)路徑必須(xu)便于旋工和投運后的(de)(de)維修。
37、制作電纜終端頭或中間接頭的(de)絕緣材料有哪些?
答:有(you)絕(jue)(jue)(jue)緣膠、絕(jue)(jue)(jue)緣帶、絕(jue)(jue)(jue)緣管、絕(jue)(jue)(jue)緣手套、絕(jue)(jue)(jue)緣樹脂等(deng)。
38、簡述電纜頭制作(zuo)的(de)一(yi)般操(cao)作(zuo)程序。答:(1)制作(zuo)前(qian)的(de)準(zhun)備:包括(kuo)○1閱(yue)讀安(an)裝說明書;○2察看(kan)現場(chang);○3備料;○4電纜試潮;○5制作(zuo)前(qian)測試等。
(2)接頭的制作過程(cheng):包(bao)括○1割斷多余電纜(lan);○2電纜(lan)保(bao)護層的剝(bo)切;○3導(dao)體連接;○4包(bao)繞(rao)絕緣(或收縮管材);○5安裝(zhuang)接頭外殼(ke);○6灌注絕緣劑;○7進行密(mi)封處理(li)等(deng)。
(3)制作后電氣測試。
39、電纜保護管的(de)加工應符合哪些(xie)要求?
答(da):(1)管口應*剌和尖銳楞角(jiao),管口宜(yi)做(zuo)成喇叭形。
(2)電纜(lan)管(guan)在彎(wan)(wan)制后,不(bu)應(ying)(ying)有(you)裂(lie)縫和顯著的凹癟(bie)現(xian)象,其彎(wan)(wan)扁(bian)程度不(bu)宜大于管(guan)子外徑10%;電纜(lan)管(guan)的彎(wan)(wan)曲半徑不(bu)應(ying)(ying)小于所穿(chuan)入電纜(lan)的最小允許彎(wan)(wan)曲半徑。
(3)金屬管應(ying)在外表(biao)涂防(fang)腐漆或瀝表(biao),鍍鋅管鋅層(ceng)剝落處也(ye)應(ying)涂以防(fang)腐漆。
40、電(dian)纜(lan)的排列符合哪些(xie)要求?答:(1)電(dian)力電(dian)纜(lan)和(he)控纜(lan)不應配置在同一層支架上。
(2)高、低(di)壓電(dian)纜(lan),強、弱電(dian)控纜(lan)應按須序分層配置,一般情況宜由(you)(you)上(shang)而下(xia),但(dan)在含有35kv以上(shang)高壓電(dian)纜(lan)引入(ru)柜盤時,為滿足彎曲半徑,可由(you)(you)下(xia)面上(shang)配置。
41、電纜溝(gou)內敷設電纜的方法(fa)是什么?
答:在(zai)電(dian)(dian)(dian)纜(lan)溝(gou)內敷(fu)設(she)電(dian)(dian)(dian)纜(lan)的方法(fa)與直埋電(dian)(dian)(dian)纜(lan)的敷(fu)設(she)方法(fa)相仿,一(yi)般可將滑輪放(fang)(fang)在(zai)溝(gou)內,施放(fang)(fang)完畢,將電(dian)(dian)(dian)纜(lan)放(fang)(fang)于溝(gou)底或支(zhi)架上,并(bing)在(zai)電(dian)(dian)(dian)纜(lan)上綁(bang)扎電(dian)(dian)(dian)纜(lan)標牌。
42、電纜(lan)敷設的常用設備(bei)有哪些(xie)?
答:(1)空氣壓縮機,主要用來破壞(huai)路面,為(wei)以后(hou)敷設(she)電纜作準(zhun)備;
(2)電(dian)動卷揚(yang)機或電(dian)纜牽引(yin)機,主要用來拖電(dian)纜;
(3)電纜輸(shu)送機,配(pei)合(he)牽(qian)引機使用來克服巨大的(de)摩擦力,減輕對電纜的(de)損壞;
(4)電纜盤放線支架;
(5)滾(gun)輪裝置(zhi);
(6)防捻 ,減(jian)鋼絲(si)繩出現的扭曲(qu);
(7)電纜(lan)盤制動裝置;
(8)張力計(ji)。
43、電纜溝中(zhong)支(zhi)架安裝(zhuang)距離的(de)(de)要求如(ru)何?答:電纜固定(ding)于(yu)電纜溝和隧道的(de)(de)墻上,水平(ping)裝(zhuang)置時,當(dang)電纜外徑(jing)等(deng)于(yu)或小于(yu)50mm時應(ying)每(mei)隔(ge)1m加一支(zhi)撐;外徑(jing)大于(yu)50mm的(de)(de)電纜每(mei)隔(ge)0.6m加一支(zhi)撐;排(pai)成(cheng)三角形的(de)(de)單電纜,每(mei)隔(ge)1m應(ying)用綁帶扎(zha)牢,垂直裝(zhuang)置時,每(mei)隔(ge)1~1.5m加以(yi)固定(ding)。
44、如何處理電(dian)力電(dian)纜(lan)與控制(zhi)電(dian)纜(lan)在同(tong)一托架的安裝?
答:電力電纜(lan)與控(kong)(kong)制電纜(lan)一(yi)般不應(ying)(ying)敷設在同一(yi)托架(jia)內,當電纜(lan)較少(shao)而將控(kong)(kong)纜(lan)與電力電纜(lan)敷設在同一(yi)托架(jia)內時,應(ying)(ying)用隔板隔開。
45、電纜隧道內如何(he)裝(zhuang)設接地線?
答:隧道和(he)溝的(de)全長應(ying)裝設連(lian)(lian)續的(de)接(jie)(jie)地線(xian),接(jie)(jie)地線(xian)應(ying)和(he)所有的(de)支(zhi)架相連(lian)(lian),兩頭和(he)接(jie)(jie)地極連(lian)(lian)通。接(jie)(jie)地線(xian)的(de)規格應(ying)符(fu)合(he)設計(ji)要求。電(dian)纜鉛包和(he)鎧裝除了有絕緣要求外,應(ying)全部(bu)相互連(lian)(lian)接(jie)(jie)并和(he)接(jie)(jie)地線(xian)相連(lian)(lian),電(dian)纜架和(he)接(jie)(jie)地線(xian)均應(ying)涂(tu)防銹(xiu)漆或鍍(du)鋅。
46、對于電纜孔洞的防(fang)火封堵有何要求?
答:對于較大(da)的電纜(lan)貫穿(chuan)孔洞(dong),如電纜(lan)貫穿(chuan)樓板處(chu)等,采用防火堵(du)料封(feng)堵(du)時,應根據實際情況(kuang),先在(zai)電纜(lan)表面涂(tu)四至(zhi)六層(ceng)防火涂(tu)料,長度(du)(du)自孔洞(dong)以下1.5m左右,再(zai)用耐火材料加(jia)工成(cheng)具(ju)有一定強度(du)(du)的板托防火堵(du)料,保(bao)證封(feng)堵(du)后(hou)牢固(gu)并便于更換電纜(lan)時拆裝,封(feng)堵(du)密實無(wu)孔隙以有效地(di)堵(du)煙堵(du)火。
47、噴燈點火前應注意哪(na)些(xie)檢查?
答:應進行下列各(ge)項檢查:
(1)打氣(qi)筒是(shi)否(fou)(fou)漏油(you)或(huo)滲(shen)油(you),油(you)桶及(ji)噴嘴處是(shi)否(fou)(fou)漏油(you)、漏氣(qi);
(2)油桶內的(de)油量(liang)是否超過油桶容量(liang)的(de)3/4,加油的(de)螺絲塞是否擰緊。
48、使用噴(pen)燈(deng)應(ying)注意(yi)哪(na)些事項?
答:(1)噴(pen)燈更大(da) 注油(you)(you)量(liang)為油(you)(you)筒容積(ji)的3/4;
(2)開始打(da)氣壓力不(bu)要太大,點燃(ran)后火焰由黃變藍即可使用;
(3)周(zhou)圍不(bu)得有(you)易燃物,空氣要流(liu)通(tong);
(4)停(ting)用時先關(guan)閉調(diao)節開(kai)關(guan),火(huo)熄(xi)后(hou),慢(man)慢(man)旋松(song)油孔蓋(gai)放氣,空氣放完(wan)后(hou),要要旋松(song)調(diao)節開(kai)關(guan),完(wan)全冷卻(que)后(hou)再旋松(song)孔蓋(gai);
(5)煤油(you)噴燈(deng)與汽油(you)噴燈(deng)要分開使用。
49、手動(dong)油壓(ya)鉗有(you)何用途?如何操作?
答:兩根導線的(de)連接通(tong)常是將兩導線端穿入(ru)相同(tong)材(cai)料(liao)制成的(de)壓(ya)(ya)管(guan)中,用壓(ya)(ya)接鉗(qian)擠壓(ya)(ya)數個坑(keng)(keng),使導線連接在一起,壓(ya)(ya)接時,手(shou)柄向上抬起時,柱(zhu)塞(sai)(sai)向外移動,進(jin)油(you)(you)(you)閥(fa)(fa)下腔產(chan)生真空,油(you)(you)(you)箱(xiang)內(nei)的(de)油(you)(you)(you)進(jin)入(ru)柱(zhu)塞(sai)(sai)腔。手(shou)柄下壓(ya)(ya)時,柱(zhu)塞(sai)(sai)向內(nei)移動,油(you)(you)(you)受壓(ya)(ya)后(hou),使進(jin)油(you)(you)(you)閥(fa)(fa)關閉,打開出(chu)油(you)(you)(you)閥(fa)(fa),使油(you)(you)(you)壓(ya)(ya)進(jin)入(ru)液壓(ya)(ya)缸,推動活(huo)塞(sai)(sai)和陽(yang)模(mo),陽(yang)、陰模(mo)之間放有壓(ya)(ya)接管(guan),當(dang)壓(ya)(ya)接被擠壓(ya)(ya)的(de)坑(keng)(keng)深到一定值時,開啟回(hui)油(you)(you)(you)閥(fa)(fa),活(huo)塞(sai)(sai)自動返回(hui),壓(ya)(ya)完一個坑(keng)(keng)后(hou),移動壓(ya)(ya)鉗(qian),再壓(ya)(ya)下一個。
50、常用低壓電(dian)(dian)力電(dian)(dian)纜按絕緣和保護層的(de)不同,主要可分為哪幾類?
答:(1)油浸紙(zhi)絕緣鉛包(或鋁包)電(dian)力電(dian)纜;
(2)不滴流油浸紙(zhi)絕緣電力電纜;
(3)聚氯(lv)乙烯絕緣(yuan)聚氯(lv)乙烯護套電力(li)電纜;
(4)交聯聚氯乙(yi)烯(xi)絕(jue)緣聚乙(yi)烯(xi)護套電力(li)電纜(lan);
(5)交聯(lian)聚(ju)氯乙烯(xi)絕緣聚(ju)氯乙烯(xi)護套電(dian)力電(dian)纜;
(6)橡皮絕緣(yuan)電(dian)力(li)電(dian)纜。
51、常用絕緣材(cai)料(liao)的(de)類別哪(na)些?舉(ju)例說明(ming)?
答:(1)無(wu)機絕緣(yuan)材料:有云母、石棉、大理石、瓷(ci)器、玻璃等;
(2)有(you)機絕緣(yuan)材(cai)料:有(you)樹脂(zhi)、橡膠、紙、麻、棉紗等(deng);
(3)混合絕(jue)(jue)緣(yuan)材料(liao)(liao):用以上(shang)絕(jue)(jue)緣(yuan)材料(liao)(liao)加(jia)工而成型的名種絕(jue)(jue)緣(yuan)材料(liao)(liao)。
52、在(zai)哪(na)種情況(kuang)下采用排管(guan)敷設?有什么優點?
答:排管敷設一(yi)般用在與其他建筑物、公路(lu)或鐵路(lu)相交叉(cha)的地(di)方,有時(shi)也在建筑物密(mi)集區內采用。主要優點是占地(di)少(shao),能承受(shou)大的荷重,電纜(lan)相互(hu)間(jian)互(hu)不(bu)影響(xiang),比(bi)較安全。
53、何謂電纜長(chang)期允(yun)許載流量?
答:電纜長期(qi)(qi)允(yun)(yun)許載流(liu)量是指在(zai)(zai)電纜內通過規定電流(liu)時(shi),在(zai)(zai)熱穩(wen)定后,電纜導(dao)體達到長期(qi)(qi)允(yun)(yun)許工作溫度時(shi)的電流(liu)數值(zhi)。
54、決定電纜(lan)長期允(yun)許(xu)載流量(liang)的因素(su)有哪些?
答:有以下三個因素決定:
(1)電纜的(de)長期容許工(gong)作(zuo)溫度;
(2)電纜本身的散熱性(xing)能;
(3)電纜裝置情況(kuang)及周圍(wei)環境的散(san)熱(re)條件。
55、電纜的敷設方(fang)式(shi)有幾種?
答:有(you)以(yi)下幾種:
(1)直(zhi)埋在地下;
(2)安裝在電纜(lan)溝內(nei);
(3)安裝在地下(xia)隧道內;
(4)安裝在建(jian)筑(zhu)物內(nei)部墻上或天棚(peng)上;
(5)安裝在橋架上;
(6)敷設在排管內;
(7)敷設在水底(di)。
56、如何進行電纜管的連接工(gong)作?
答:電纜管(guan)連(lian)接(jie)(jie)(jie)時(shi),必須用扣和(he)管(guan)接(jie)(jie)(jie)頭連(lian)接(jie)(jie)(jie),如采用焊(han)接(jie)(jie)(jie)時(shi),不能直接(jie)(jie)(jie)對焊(han),連(lian)接(jie)(jie)(jie)處要套(tao)上一段粗管(guan)再進行焊(han)接(jie)(jie)(jie),以免焊(han)渣掉入管(guan)內。
57、制作電纜頭時,對上(shang)下扳(ban)彎電纜芯線有(you)何要求?
答:扳彎線芯(xin)時,不得(de)損傷紙(zhi)絕緣,芯(xin)線的(de)彎曲(qu)半徑不得(de)小于電纜線芯(xin)的(de)10倍。制作(zuo)時要特別小心,應使線芯(xin)彎曲(qu)部分均(jun)勻受力,否則(ze)極易(yi)損傷絕緣紙(zhi)。
58、簡(jian)述塑(su)料(liao)電纜的熱收縮密封法。
答(da):熱(re)縮(suo)法(fa)適用(yong)(yong)于中、低(di)壓橡(xiang)、塑(su)電(dian)纜(lan)接頭(tou)和終(zhong)端頭(tou)的密封,也可適用(yong)(yong)于不滴流和黏性浸漬絕(jue)緣電(dian)纜(lan)。采用(yong)(yong)交聯聚乙烯(xi)型和硅橡(xiang)膠型兩大類遇熱(re)后(hou)能均勻收(shou)縮(suo)的熱(re)收(shou)縮(suo)管(guan)。將這(zhe)種管(guan)材(cai)套于預(yu)定的粘合密封部位,并在粘和部位涂上熱(re)熔膠,當加熱(re)到一定溫度后(hou),熱(re)縮(suo)管(guan)將收(shou)縮(suo),同時熱(re)熔膠熔化(hua),待自然冷(leng)卻后(hou)即形成一道良好的密封封層(ceng)。
59、用電(dian)動彎管(guan)機彎制(zhi)電(dian)纜保護(hu)管(guan)時應注意什(shen)么?
答:(1)彎管機應(ying)由了解其性能(neng)并(bing)熟(shu)悉(xi)操(cao)作知識的(de)人員(yuan)操(cao)作;
(2)使用前(qian)必須進行檢(jian)查,按鈕、操作把手、行程開關應完好(hao),彎管機必須可靠接地;
(3)選(xuan)用符合要求的(de)模具,確定好所需(xu)要的(de)彎曲半徑;
(4)施工場(chang)地周圍(wei),應有充(chong)足的活動范(fan)圍(wei);
(5)使用時待(dai)空(kong)轉正常(chang)后(hou),方可(ke)帶負(fu)荷工(gong)作,運行中,嚴禁用手腳接觸其轉動部分(fen);
(6)工作完(wan)畢應及時停電,釋放油壓。
60、電(dian)纜(lan)清冊的內容(rong)及電(dian)纜(lan)編號的含義是什么(me)?
答:電纜(lan)清冊是施放電纜(lan)和指(zhi)導施工的依(yi)據(ju),運行維(wei)護的檔案(an)資料。應列入每(mei)根(gen)電纜(lan)的編號(hao)、起始點、型號(hao)、規格、長度(du),并分類(lei)統(tong)計出總長度(du),控纜(lan)還應列出每(mei)根(gen)電纜(lan)的備用芯。
電纜編號是識別(bie)電纜的(de)標志,故(gu)要(yao)求全(quan)廠編號不重復(fu),并且有一定的(de)含(han)義和(he)規律,能(neng)表達電纜的(de)特征。
61、電纜(lan)目前采用的敷設方(fang)法可分(fen)為幾(ji)類?
答:(1)人(ren)工敷設(she),即采用人(ren)海戰術(shu),在(zai)一人(ren)或多人(ren)協(xie)調指揮(hui)下,按規定進行敷設(she);
(2)機(ji)械(xie)化敷設,即采用滾輪、牽引器、輸送機(ji),通過一同(tong)步電源進行控制,比(bi)較安全;
(3)人工和機械(xie)相結合,有些現(xian)場由于轉彎(wan)較多,施工難度大(da),全(quan)用(yong)機械(xie)較困難,所以(yi)采(cai)用(yong)此法。
62、控制二次回路(lu)接線(xian)應符合哪些要求(qiu)?
答(da):(1)按圖施工接(jie)線正確;
(2)導線的電氣連接應牢固可靠;
(3)盤柜內的導線不應有接頭,導線芯線應無損傷;
(4)電纜芯線(xian)端(duan)部應標明其回(hui)路(lu)編號(hao),編號(hao)應正確,字跡清晰且不易脫(tuo)色;
(5)配線(xian)應整(zheng)齊(qi)、清晰(xi)、美觀,導線(xian)絕緣應良好、無損;
(6)每(mei)個接線(xian)端子的每(mei)側(ce)接線(xian)宜為一根,最多(duo)不得超(chao)過兩根。
63、電纜排管有何(he)要求?
答:(1)排管頂部至地面距離,在廠房(fang)內為0.2m,人行道下為0.5m,一般地區為0.7m;
(2)在(zai)變更方(fang)向及分支處均應(ying)裝(zhuang)置(zhi)排管井坑,長度超過(guo)30mm時也應(ying)加(jia)設(she)井坑;
(3)井坑深(shen)度不小于0.8m,人(ren)孔直徑不小于0.7mm;
(4)排管應有傾向井坑(keng)0.5%~1%的排水坡度。
64、對于電纜導體(ti)連(lian)接點的電阻有何要求?
答:要求連接(jie)點(dian)的(de)電阻小(xiao)而且穩定,連接(jie)點(dian)的(de)電阻與(yu)相(xiang)(xiang)同(tong)長度、相(xiang)(xiang)同(tong)截(jie)面的(de)導體(ti)之比(bi)值,對(dui)(dui)于新(xin)安裝的(de)終(zhong)端頭(tou)和中間頭(tou),應(ying)不(bu)大于1;對(dui)(dui)于運行中的(de)終(zhong)端頭(tou)和中間頭(tou)這個比(bi)值不(bu)應(ying)大于1.2。
65、電纜接頭和(he)中間頭的設(she)計應(ying)滿(man)足哪些要(yao)求?
答:應滿足的要求(qiu)有:
(1)耐壓(ya)強度高,導體連接好;
(2)機械強度大(da),介(jie)質損失小;
(3)結構(gou)簡(jian)單,密封(feng)性強。
66、什么是電(dian)纜故(gu)障?有(you)幾種常(chang)見的類型?
答(da):電(dian)纜故(gu)(gu)障(zhang)(zhang)是(shi)指(zhi)電(dian)纜在預防性(xing)試驗(yan)時發生絕緣擊穿或在運行中,因絕緣擊穿、導線(xian)(xian)燒(shao)斷(duan)等而迫使電(dian)纜線(xian)(xian)路停電(dian)的(de)故(gu)(gu)障(zhang)(zhang)。常見的(de)故(gu)(gu)障(zhang)(zhang)有(you)接地故(gu)(gu)障(zhang)(zhang)、短(duan)路故(gu)(gu)障(zhang)(zhang)、斷(duan)線(xian)(xian)故(gu)(gu)障(zhang)(zhang)、閃絡性(xing)故(gu)(gu)障(zhang)(zhang)和(he)混合型故(gu)(gu)障(zhang)(zhang)等。
67、如何處(chu)理電(dian)纜線(xian)路的單相接(jie)地故障?
答:電(dian)(dian)纜(lan)線路單相(xiang)接(jie)地故障一般來說,電(dian)(dian)纜(lan)導體的損傷只是(shi)局(ju)部的,如果(guo)屬于機械(xie)損傷,而故障點附(fu)近的土壤又較干燥時,一般可(ke)進(jin)行(xing)局(ju)部修(xiu)理,加添(tian)一只假接(jie)頭,即不(bu)將電(dian)(dian)纜(lan)芯(xin)鋸(ju)斷(duan),僅將故障點絕緣加強后密封(feng)即可(ke)。
68、電力電纜在敷設前應進行哪(na)些試驗和檢查?
答:敷設前應檢查電纜的型號、規格及長度是(shi)否符合要(yao)求,是(shi)否有(you)外力(li)損(sun)傷,低(di)壓(ya)電纜用1000V兆歐表(biao)遙測絕緣電阻(zu)(zu),阻(zu)(zu)值一般不(bu)低(di)于(yu)10MΩ,高壓(ya)電纜用2500V兆歐表(biao)搖測阻(zu)(zu)值一般不(bu)抵于(yu)400MΩ。
69、主廠房(fang)內敷(fu)設電(dian)纜時(shi)一般(ban)應注意什么?
答(da):在主廠房內敷設電纜時一般應注意:
(1)凡引至集控室的控制電纜宜架空敷設;
(2)6KV電纜宜用(yong)隧道或排(pai)管敷設(she),地下水位高處(chu)亦可架空或用(yong)排(pai)管敷設(she);
(3)380V電(dian)纜當(dang)(dang)兩端(duan)電(dian)纜在(zai)零米時宜(yi)用隧道、溝或排管,當(dang)(dang)一(yi)端(duan)設備在(zai)上、一(yi)端(duan)在(zai)下時,可部分架空敷設,當(dang)(dang)地下水位較(jiao)高時,宜(yi)架空。
70、電力電纜的(de)內屏蔽層與外屏蔽層各(ge)在什么(me)部位?采(cai)用(yong)什么(me)材料?有何作用(yong)?
答:為了(le)(le)使絕(jue)緣層和電纜導體有(you)(you)(you)較好的(de)(de)接(jie)觸,消除導體表面的(de)(de)不光滑引起的(de)(de)導體表面電場強度的(de)(de)增(zeng)加(jia),一般在導體表面包有(you)(you)(you)金(jin)屬(shu)化紙(zhi)或(huo)半(ban)導體紙(zhi)帶的(de)(de)內屏蔽層。為了(le)(le)使絕(jue)緣層和金(jin)屬(shu)護套有(you)(you)(you)較好的(de)(de)接(jie)觸,一般在絕(jue)緣層外(wai)表面包有(you)(you)(you)外(wai)層屏蔽層。外(wai)屏層與內屏層的(de)(de)材料相同(tong),有(you)(you)(you)時(shi)還外(wai)扎銅(tong)帶或(huo)編織銅(tong)絲(si)帶。
71、簡述環氧樹脂(zhi)復(fu)合物的構成(cheng)及性(xing)能。
答(da):環氧樹(shu)脂復合(he)物由環氧樹(shu)脂加入硬化劑(ji)、填充(chong)劑(ji)增韌劑(ji)和稀釋(shi)劑(ji)組成(cheng)。具有以下性能:
(1)有足夠(gou)的(de)機械(xie)強度(du);
(2)電氣(qi)性能(neng)優良;
(3)電氣性能穩定;
(4)與有色(se)金屬有足(zu)夠(gou)的黏附力;
(5)耐腐(fu)蝕(shi)性好;
(6)戶外使用時(shi),耐(nai)雨、耐(nai)光(guang)、耐(nai)濕熱。
72、單芯電纜護套(tao)一(yi)端接地方(fang)式中為什么必須安(an)裝一(yi)條沿電纜平(ping)行(xing)敷設的回(hui)流(liu)線?
答:在金屬護套一(yi)端(duan)(duan)接地(di)的電纜線路中,為確保護套中的感應電壓不超過允許標準,必須安(an)裝一(yi)條沿電纜線路平行敷設(she)的導體(ti),且導體(ti)的兩端(duan)(duan)接地(di),這(zhe)種(zhong)導體(ti)稱為回(hui)流(liu)(liu)(liu)線。當(dang)發生單相接地(di)故障時(shi)(shi),接地(di)短路電流(liu)(liu)(liu)可(ke)(ke)以通過回(hui)流(liu)(liu)(liu)線流(liu)(liu)(liu)回(hui)系統中心(xin)點,由于通過回(hui)流(liu)(liu)(liu)線的接地(di)電流(liu)(liu)(liu)產生的磁通抵消了一(yi)部(bu)分電纜導線接地(di)電流(liu)(liu)(liu)所產生的磁通,因而可(ke)(ke)降低(di)短路故障時(shi)(shi)護套的感應電壓。
73、電纜(lan)工程可(ke)劃(hua)分為(wei)幾個項目?
答(da):(1)工(gong)地運(yun)輸:包括工(gong)程(cheng)材料從倉(cang)庫到施工(gong)點的裝(zhuang)卸、運(yun)輸和(he)空車回程(cheng)。
(2)地方工程(cheng):包括路面開挖、隧、溝道施工等(deng)。
(3)敷(fu)(fu)設(she)工程:包(bao)括敷(fu)(fu)設(she)、中(zhong)間(jian)頭制(zhi)作、掀(xian)蓋板、埋管、校潮、牽引頭制(zhi)作等(deng)。
(4)兩端(duan)工(gong)程:包括支、吊橋架(jia)和其基礎(chu)的制作(zuo)安裝(zhuang)(zhuang),終端(duan)頭制作(zuo),油壓力和信號(hao)裝(zhuang)(zhuang)置的安裝(zhuang)(zhuang),名種電氣性能(neng)測試等。
(5)塞(sai)止工程:包括充油電(dian)纜塞(sai)止頭制作(zuo),供油箱、自(zi)動排水及信(xin)號裝置的安裝等。
(6)接地工程:包括(kuo)絕緣接頭(tou)、換位箱、保(bao)護器、接地箱安裝等。
74、電(dian)纜(lan)線路的驗(yan)收應進(jin)行哪些檢(jian)查?
答:(1)電(dian)纜(lan)規格應符合(he)規定,排列應整齊,無損傷,標牌齊全、正確(que)、清晰;
(2)電(dian)纜的(de)固(gu)定彎(wan)曲半徑、有關距離及單芯電(dian)力電(dian)纜的(de)金屬護層的(de)接(jie)線(xian)應符(fu)合要求(qiu);
(3)電纜(lan)終(zhong)端、中間頭(tou)不滲漏油(you),安裝牢固,充油(you)電纜(lan)油(you)壓及(ji)表計整(zheng)定值應(ying)符合要求(qiu);
(4)接地(di)良好;
(5)電纜終端相色正(zheng)確,支架等的(de)金屬(shu)部件油漆完整;
(6)電纜溝及隧道內、橋(qiao)架上應無雜物,蓋(gai)板齊全。
75、電(dian)纜(lan)線路正序(xu)阻(zu)抗測量(liang)過程中有什么要求?
答(da):電纜導體(ti)的(de)交(jiao)流電阻(zu)和電纜三相(xiang)同感抗的(de)相(xiang)量和稱(cheng)為正序阻(zu)抗。
電纜(lan)線路的(de)正(zheng)序阻抗一般(ban)(ban)可(ke)在電纜(lan)盤上(shang)直接測量,測量時(shi)一般(ban)(ban)使用(yong)(yong)較(jiao)低的(de)電壓(ya),因此,需要(yao)用(yong)(yong)降壓(ya)變壓(ya)器(qi)進行(xing)降壓(ya),降壓(ya)器(qi)采(cai)用(yong)(yong)星形接線,容量一般(ban)(ban)為10kVA以上(shang),有(you)較(jiao)廣的(de)電壓(ya)調節范圍,測量時(shi)交(jiao)流(liu)(liu)(liu)電源應比(bi)較(jiao)穩(wen)定,以保證(zheng)測量時(shi)電流(liu)(liu)(liu)達到規定的(de)要(yao)求(qiu),實(shi)際電壓(ya)表的(de)讀數(shu)值必須是電纜(lan)端的(de)電壓(ya),試(shi)驗電流(liu)(liu)(liu)更好 接近電纜(lan)長期允許(xu)載流(liu)(liu)(liu)量,測讀各表計的(de)數(shu)值時(shi),合(he)上(shang)電流(liu)(liu)(liu)后(hou)同(tong)時(shi)讀取三個表的(de)數(shu)值。
76、根據《電業生產(chan)安全規定(ding)》,電氣工作人(ren)員必須具備的條件是什么?
答:必須具備(bei)下列(lie)條件:
(1)經醫生鑒定(ding)身體(ti)健(jian)康(kang),無妨礙工作的(de)病癥;
(2)具備必要的(de)電(dian)氣(qi)知識,按其職務和工作性質(zhi)掌(zhang)握相關(guan)的(de)規程、專業技術(shu)及安全操作技術(shu),并(bing)經考試合格(ge);
(3)熟練掌握(wo)觸電急(ji)救方法。
77、電(dian)纜在運(yun)輸裝卸(xie)過程中應(ying)注意什么(me)?
答:(1)在(zai)運輸裝(zhuang)卸過(guo)程(cheng)中,不(bu)應(ying)使電(dian)纜(lan)及電(dian)纜(lan)盤受到損傷,嚴禁將電(dian)纜(lan)盤直接由車上推下,電(dian)纜(lan)般不(bu)應(ying)平放(fang)(fang)運輸,平放(fang)(fang)貯存(cun)。
(2)運輸或滾(gun)動電(dian)(dian)纜盤(pan)前,必須保證電(dian)(dian)纜盤(pan)牢固(gu),電(dian)(dian)纜繞緊、充(chong)油(you)(you)電(dian)(dian)纜至壓(ya)(ya)力(li)油(you)(you)箱(xiang)間的油(you)(you)管(guan)應(ying)(ying)固(gu)定,不得損(sun)傷,壓(ya)(ya)力(li)油(you)(you)箱(xiang)應(ying)(ying)牢固(gu),壓(ya)(ya)力(li)指示應(ying)(ying)符合(he)要求。
78、電纜防(fang)火有哪些措施?
答(da):(1)采用阻(zu)燃電纜(lan);
(2)采(cai)用防火電(dian)纜托架;
(3)采用防(fang)火涂料;
(4)電纜隧道、夾層出口等處設置防(fang)火隔墻、防(fang)火擋板(ban);
(5)架(jia)空(kong)電纜應避(bi)開油管道、防(fang)爆門,否(fou)則應有要取局部穿管或隔熱防(fang)火措(cuo)施(shi)。
79、選擇電力電纜(lan)的截面應從哪幾個方(fang)面考慮?
答:應考(kao)慮如下幾個(ge)方面:
(1)電(dian)纜長期允(yun)許通過的工作電(dian)流(liu);
(2)一旦短路時的熱穩(wen)定性;
(3)線路上的電壓降(jiang)不能超出允許工作范(fan)圍。
80、電力電纜和架空線(xian)比較有(you)哪些優點(dian)?
答:(1)運(yun)行可靠,由于(yu)安裝(zhuang)在地下等(deng)隱蔽處,受外力(li)破(po)壞小,發生故障的機會(hui)較(jiao)少,供(gong)電安全,不會(hui)給人身造成危害;
(2)維護工作量小(xiao),不需(xu)頻(pin)繁的(de)巡檢;
(3)不需架設桿塔;
(4)有(you)助(zhu)于(yu)提高功(gong)率因(yin)數。