1、常(chang)用的電線、電纜(lan)按用途(tu)分有哪些種類(lei)?
答:按用途可分為(wei)裸導線(xian)、絕緣電(dian)(dian)(dian)線(xian)、耐熱電(dian)(dian)(dian)線(xian)、屏蔽電(dian)(dian)(dian)線(xian)、電(dian)(dian)(dian)力電(dian)(dian)(dian)纜(lan)、控制電(dian)(dian)(dian)纜(lan)、通信電(dian)(dian)(dian)纜(lan)、射頻電(dian)(dian)(dian)纜(lan)等。
2、絕緣電線有(you)哪幾種?
答:常有(you)的絕(jue)緣(yuan)電線(xian)(xian)(xian)有(you)以下幾種:聚氯乙(yi)烯絕(jue)緣(yuan)電線(xian)(xian)(xian)、聚氯乙(yi)烯絕(jue)緣(yuan)軟(ruan)(ruan)線(xian)(xian)(xian)、丁(ding)腈聚氯乙(yi)烯混合物絕(jue)緣(yuan)軟(ruan)(ruan)線(xian)(xian)(xian)、橡皮絕(jue)緣(yuan)電線(xian)(xian)(xian)、農用地(di)下直埋鋁芯塑料絕(jue)緣(yuan)電線(xian)(xian)(xian)、橡皮絕(jue)緣(yuan)棉紗紡織(zhi)軟(ruan)(ruan)線(xian)(xian)(xian)、聚氯乙(yi)烯絕(jue)緣(yuan)尼(ni)龍護(hu)套電線(xian)(xian)(xian)、電力(li)和照明用聚氯乙(yi)烯絕(jue)緣(yuan)軟(ruan)(ruan)線(xian)(xian)(xian)等。
3、電(dian)纜橋架適合于何(he)種場合?
答:電(dian)纜橋架(jia)適用(yong)于(yu)一般(ban)工礦企業(ye)室(shi)內外(wai)架(jia)空敷設電(dian)力電(dian)纜、控制電(dian)纜,亦可用(yong)于(yu)電(dian)信、廣播電(dian)視(shi)等部門(men)在室(shi)內外(wai)架(jia)設。
4、電纜附件(jian)有(you)哪些?
答:常(chang)用的電(dian)附件有電(dian)纜(lan)(lan)終端接(jie)線(xian)(xian)盒(he)、電(dian)纜(lan)(lan)中間接(jie)線(xian)(xian)盒(he)、連接(jie)管(guan)及(ji)接(jie)線(xian)(xian)端子(zi)、鋼板接(jie)線(xian)(xian)槽(cao)、電(dian)纜(lan)(lan)橋架等。
5、什(shen)么叫電(dian)纜中間接頭?
答:連接電(dian)纜與電(dian)纜的導體、絕緣屏蔽層和保(bao)護層,以使電(dian)纜線路連接的裝置,稱為電(dian)纜中(zhong)間接頭(tou)。
6、什么叫電氣(qi)主(zhu)接(jie)線?
答:電氣主接(jie)線是發電廠、變電所中主要(yao)電氣設備和母線的連接(jie)方式(shi),包括主母線和廠用電系統(tong)按(an)一定(ding)的功能要(yao)求的連接(jie)方式(shi)。
7、在(zai)選擇(ze)電(dian)(dian)力電(dian)(dian)纜的截面(mian)時,應遵照哪些規定?
答:電(dian)(dian)力電(dian)(dian)纜(lan)的選擇應遵照以下原則:(1)電(dian)(dian)纜(lan)的額定(ding)電(dian)(dian)壓要大于或等于安裝點供(gong)電(dian)(dian)系統(tong)的額定(ding)電(dian)(dian)壓;(2)電(dian)(dian)纜(lan)持(chi)續容許電(dian)(dian)流(liu)應等于或大于供(gong)電(dian)(dian)負載的更大 持(chi)續電(dian)(dian)流(liu);(3)線芯截面(mian)要滿足供(gong)電(dian)(dian)系統(tong)短路時的穩定(ding)性的要求;(4)根據電(dian)(dian)纜(lan)長度驗算電(dian)(dian)壓降(jiang)是否符(fu)合要求;(5)線路末端(duan)的最(zui)小(xiao)短路電(dian)(dian)流(liu)應能使保護裝置可(ke)靠的動作(zuo)。
8、交(jiao)聯聚(ju)乙烯電(dian)纜和油紙(zhi)電(dian)纜比(bi)較(jiao)有哪些優點?
答:(1)易安裝,因為(wei)(wei)它允(yun)許(xu)最小彎(wan)曲半徑小、且重量輕;(2)不受線(xian)路落差*;(3)熱(re)性(xing)(xing)能好,允(yun)許(xu)工作(zuo)溫度高、傳(chuan)輸容(rong)量大;(4)電(dian)纜附(fu)件簡單,均為(wei)(wei)干式結(jie)構;(5)運行(xing)維護簡單,無漏油問題;(6)價(jia)格較(jiao)低;(7)可靠性(xing)(xing)高、故障率低;(8)制(zhi)造工序少、工藝簡單,經濟效益(yi)顯著(zhu)。
9、固定交流單芯電纜的夾具有什么要求?為什么?
答:夾(jia)具(ju)應(ying)無鐵(tie)件(jian)(jian)構成閉(bi)合磁路,這是因為當電(dian)纜線(xian)(xian)(xian)芯(xin)通過電(dian)流時,在(zai)(zai)其周圍產生磁力線(xian)(xian)(xian),磁力線(xian)(xian)(xian)與通過線(xian)(xian)(xian)芯(xin)的(de)電(dian)流大小成正比,若使用鐵(tie)件(jian)(jian)等導(dao)磁材料,根據電(dian)磁感(gan)應(ying)可(ke)知,將(jiang)在(zai)(zai)鐵(tie)件(jian)(jian)中產生渦流使電(dian)纜發熱,甚至燒壞電(dian)纜。所以不可(ke)使用鐵(tie)件(jian)(jian)作(zuo)單(dan)芯(xin)交流電(dian)纜的(de)固定夾(jia)具(ju)。
10、以下的(de)熱縮(suo)電纜頭的(de)附件的(de)更大 特點和優點是什(shen)么?
答:熱縮(suo)附(fu)件(jian)的更大 特點是用應(ying)力(li)管代(dai)替傳統的應(ying)力(li)錐,它不僅簡化了施工工藝,還縮(suo)小(xiao)了接頭的終端的尺寸,安裝(zhuang)方便(bian),省(sheng)時省(sheng)工,性(xing)能(neng)優越,節約(yue)金屬。熱縮(suo)電纜附(fu)件(jian)集(ji)灌注式和干(gan)包式為一體,集(ji)合了這兩種(zhong)附(fu)件(jian)的優點。
11、電(dian)纜(lan)敷設前應(ying)進行哪些檢查工(gong)作?
答:(1)支架應齊(qi)全、油(you)漆完整。(2)電纜(lan)型號、電壓(ya)、規(gui)格(ge)符合(he)設計。(3)電纜(lan)絕緣(yuan)良好,當對油(you)紙電纜(lan)的密封有懷疑時,應進(jin)行受(shou)潮判斷(duan);直埋電纜(lan)與小底電纜(lan)應經直流(liu)耐(nai)壓(ya)試難合(he)格(ge);充油(you)電纜(lan)的油(you)樣(yang)應試驗合(he)格(ge)。(4)充油(you)電纜(lan)的油(you)壓(ya)不宜低于(yu)1.47MPa。
11、交聯熱收縮(suo)電纜附件有哪些優點(dian)?
答(da):這是一種新型(xing)材料(liao),它與現在其(qi)他類型(xing)附件比較具(ju)有電(dian)氣(qi)性(xing)能(neng)優越、體積小、質量小、安裝簡便、材料(liao)配套等優點,另外還(huan)具(ju)有耐氣(qi)候、抗污穢性(xing)、阻燃自熄等能(neng)力(li)。
12、對油紙絕緣電(dian)(dian)力電(dian)(dian)纜(lan)(lan)密封(feng)有懷疑時,如何(he)用較簡(jian)單的辦法檢查電(dian)(dian)纜(lan)(lan)絕緣紙是否受(shou)潮?
答:把電纜絕緣紙(zhi)點燃或放(fang)入150℃左(zuo)右的電纜油(you)中檢(jian)查,無“嘶(si)嘶(si)”聲或白色泡沫出現,說明未受潮。
13、電纜標志(zhi)牌應注(zhu)明什么內容(rong)?編寫有何要求?
答:標志牌上(shang)應(ying)注明電(dian)纜線路(lu)設計編號(hao)(hao)、電(dian)纜型號(hao)(hao)、規格及始(shi)點,并聯使用的電(dian)纜應(ying)有順序號(hao)(hao)。要求(qiu)字跡清晰、不(bu)易脫(tuo)落。
14、直(zhi)埋電纜的方位標志應(ying)設(she)置(zhi)在哪(na)些位置(zhi)?
答:在(zai)電(dian)纜(lan)兩端,電(dian)纜(lan)直(zhi)線段(duan)50~100m處(chu)(chu)電(dian)纜(lan)接頭幾電(dian)纜(lan)改變方向的(de)彎角處(chu)(chu)。
15、制作電纜接頭(tou)用的黃臘綢帶、黑玻璃漆帶、無堿玻璃絲(si)帶等,施工前如何進(jin)行排潮處理?
答:(1)恒(heng)溫(wen)(wen)干燥(zao)法(fa):將(jiang)(jiang)絕緣帶卷(juan)成直徑為25~30mm小卷(juan),放入(ru)110~120℃恒(heng)溫(wen)(wen)干燥(zao)箱內(nei)烘4~5h,冷卻(que)干取(qu)出(chu),放入(ru)干燥(zao)的(de)(de)密封筒內(nei)。(2)油(you)(you)浸排潮法(fa):將(jiang)(jiang)絕緣帶小卷(juan)放入(ru)恒(heng)溫(wen)(wen)在120~130℃的(de)(de)電(dian)纜油(you)(you)中(zhong),離(li)鍋底保持30mm距離(li),經一定時間后油(you)(you)面(mian)不再(zai)產生(sheng)泡沫后取(qu)出(chu),裝入(ru)貯有電(dian)纜油(you)(you)的(de)(de)桶中(zhong),油(you)(you)位應超過所(suo)有裝入(ru)的(de)(de)物(wu)體(ti)并將(jiang)(jiang)其(qi)密封。
16、電纜(lan)外護層的作用是什么?
答:保護(hu)內護(hu)層不受機械(xie)損(sun)傷和(he)化學腐蝕(shi),增強機械(xie)強度。
17、室(shi)外電(dian)纜溝應符合(he)哪些要求?
答(da):電纜溝上部應比地面稍高(gao),加蓋(gai)用混凝土制作的蓋(gai)板,電纜應平敷在支架上,有良(liang)好的排水管。
18、電(dian)纜內護層的(de)作(zuo)用是什么?
答;使絕緣層不會與水、空(kong)氣或其他物體接觸,防止(zhi)絕緣受(shou)潮和絕緣層不受(shou)機械傷害。
19、使用鋼絲鉗時(shi)應注意(yi)些什么?
答:使用前,一定要檢(jian)查絕(jue)(jue)緣(yuan)(yuan)柄的絕(jue)(jue)緣(yuan)(yuan)是否完好無(wu)損,使用時(shi)不(bu)可用鋼(gang)絲鉗(qian)剪切(qie)超過(guo)規格所允許的金屬線材,并禁止(zhi)用鋼(gang)絲鉗(qian)代替(ti)錘子(zi)敲(qiao)打工具,以免損壞。
20、什么叫絕緣強度(du)?
答:絕緣物質在電(dian)場中,當電(dian)場強度增(zeng)大到(dao)某一極限時(shi)就會被擊穿(chuan),這個導(dao)致絕緣擊穿(chuan)的電(dian)場強度稱為絕緣強度。
22、對(dui)電纜(lan)導體連接點(dian)的(de)機(ji)械強(qiang)度(du)有何(he)要求?
答:連接點的機(ji)械強(qiang)度,一般低(di)于(yu)(yu)電(dian)纜導體本身(shen)的抗拉(la)(la)強(qiang)度,對于(yu)(yu)固(gu)定(ding)敷設的電(dian)力(li)電(dian)纜,其連接點的抗拉(la)(la)強(qiang)度要求不低(di)于(yu)(yu)導體本身(shen)抗拉(la)(la)強(qiang)度的60%。
23、電力電纜的絕緣層材料應(ying)具(ju)備哪些主要性能?
答;應具備下列主(zhu)要(yao)性(xing)(xing)能(neng)(neng):(1)高的(de)擊穿強度;(2)低的(de)介質損(sun)耗;(3)相當高的(de)絕(jue)緣(yuan)電(dian)阻(zu);(4)優(you)良(liang)的(de)耐放電(dian)性(xing)(xing)能(neng)(neng);(5)具有一定(ding)(ding)的(de)柔(rou)軟性(xing)(xing)和機(ji)械強度;(6)絕(jue)緣(yuan)性(xing)(xing)能(neng)(neng)長(chang)期穩(wen)定(ding)(ding)。
24、機械敷設電纜時(shi),牽引強(qiang)度有何(he)規定?
答:對于(yu)銅(tong)芯電纜(lan)(lan),當(dang)(dang)牽(qian)(qian)引(yin)(yin)頭部時,允(yun)許牽(qian)(qian)引(yin)(yin)強(qiang)度為70N/cm;對于(yu)鋁芯電纜(lan)(lan),當(dang)(dang)牽(qian)(qian)引(yin)(yin)頭部時,允(yun)許牽(qian)(qian)引(yin)(yin)強(qiang)度為40N/cm;若利用鋼絲(si)網套牽(qian)(qian)引(yin)(yin)時,鉛(qian)護套電纜(lan)(lan)允(yun)許強(qiang)度為10N/cm;鉛(qian)護套電纜(lan)(lan)為40N/cm。
25、對電纜(lan)保護(hu)管有(you)何規定?
答:(1)電(dian)(dian)纜需要穿保護管敷設時,管子內(nei)徑不(bu)應小于(yu)電(dian)(dian)纜外徑的1.5倍,混凝(ning)土(tu)(tu)管、陶土(tu)(tu)管、石棉、水泥(ni)管的內(nei)徑不(bu)應小于(yu)100mm;
(2)電(dian)纜管的彎曲半(ban)徑(jing)應符合所穿入電(dian)纜彎曲半(ban)徑(jing)的規定(ding);
(3)每根管子最多不(bu)(bu)應超過三個彎(wan)頭,直(zhi)角彎(wan)不(bu)(bu)應多于2個。
26、如何測(ce)量(liang)電纜護套(tao)的(de)外徑?
答:在護(hu)套(tao)圓周上均勻分布的五點處,測量護(hu)套(tao)外徑和其平均值,其平均外徑既為護(hu)套(tao)的外徑。
27、不同截面(mian)的銅芯電纜如何(he)連(lian)接(jie)?
答:不(bu)同(tong)(tong)截面的(de)銅芯(xin)電纜連接(jie),可采(cai)用開口弱背銅接(jie)管(guan),以錫焊(han)法連接(jie),也(ye)可用純銅棒(bang)按不(bu)同(tong)(tong)的(de)截面要求(qiu)連接(jie)成銅接(jie)管(guan),以壓(ya)接(jie)法連接(jie)。
28、簡述10KV交聯電(dian)纜熱縮(suo)式(shi)制作戶內終端(duan)頭的(de)過程?
答;(1)準備階段:檢(jian)查熱縮(suo)電纜(lan)附(fu)件是(shi)否齊備,型號是(shi)否相配,檢(jian)查并確認電纜(lan)有無潮氣后,檢(jian)查電纜(lan)。
(2)切(qie)除(chu)多余電(dian)纜(lan),根據現場情況決定電(dian)纜(lan)長(chang)度。
(3)剝(bo)除護層。
(4)焊接(jie)接(jie)地(di)(di)線,將(jiang)接(jie)地(di)(di)線焊接(jie)在(zai)鋼帶上。
(5)填充三叉口(kou)及(ji)繞包密封(feng)膠。
(6)安裝三芯分支護(hu)套(tao),將(jiang)護(hu)套(tao)套(tao)入(ru)根部(bu),從中部(bu)開始收(shou)縮,先往根部(bu),再往指(zhi)部(bu)。
(7)剝(bo)(bo)銅 帶(dai)和外半導電層(ceng),剝(bo)(bo)切三芯分支套口20mm以上的銅帶(dai),嚴禁(jin)損傷主(zhu)絕緣,清除干(gan)凈半導電層(ceng)。
(8)安裝應力管(guan)(guan),管(guan)(guan)口端部(bu)分支套對接(jie)后熱縮。
(9)安裝接線端子。
(10)安裝絕緣管(guan)。
(11)安裝密(mi)封管。
(12)核相后安裝相色管。
29、戶內、戶外預(yu)制式終端安(an)裝(zhuang)步驟有哪些?
答:(1) 將(jiang)電纜按預(yu)定位置就(jiu)位、固(gu)定、清(qing)潔表面,參照說明書剝(bo)除(chu)外護(hu)套,如有(you)特殊需要,外護(hu)套剝(bo)切長度(du)可調(diao)整(zheng),分(fen)別由銅帶、外護(hu)套鎧裝(zhuang)引(yin)出2組地線(xian)。
(2) 由(you)外護套口(kou)(kou)向(xiang)上(shang)量(liang)取(qu)需要尺(chi)寸,切除多(duo)余電纜,套入熱縮(suo)三指套至三叉(cha)口(kou)(kou)根部(bu)由(you)中(zhong)間加熱收縮(suo),由(you)指套上(shang)口(kou)(kou)向(xiang)上(shang)量(liang)取(qu)規定尺(chi)寸(35kv為350~380mm)。去掉多(duo)余銅帶(保(bao)留(liu)20mm),再保(bao)留(liu)半(ban)導體預定位置(zhi),壓接(jie)出線端(duan)子密封。
30、電線電纜(lan)的應(ying)用主要分為(wei)三(san)大(da)類(lei) :
(1)、電力系統
電(dian)(dian)(dian)(dian)力(li)(li)系統采用的(de)電(dian)(dian)(dian)(dian)線(xian)(xian)電(dian)(dian)(dian)(dian)纜(lan)(lan)(lan)產品主(zhu)要有(you)架空裸(luo)電(dian)(dian)(dian)(dian)線(xian)(xian)、匯(hui)流排(母線(xian)(xian))、電(dian)(dian)(dian)(dian)力(li)(li)電(dian)(dian)(dian)(dian)纜(lan)(lan)(lan)(塑料線(xian)(xian)纜(lan)(lan)(lan)、油(you)紙力(li)(li)纜(lan)(lan)(lan)(基本被塑料電(dian)(dian)(dian)(dian)力(li)(li)電(dian)(dian)(dian)(dian)纜(lan)(lan)(lan)代替)、橡套(tao)線(xian)(xian)纜(lan)(lan)(lan)、架空絕緣電(dian)(dian)(dian)(dian)纜(lan)(lan)(lan))、分支(zhi)電(dian)(dian)(dian)(dian)纜(lan)(lan)(lan)(取代部分母線(xian)(xian))、電(dian)(dian)(dian)(dian)磁線(xian)(xian)以及電(dian)(dian)(dian)(dian)力(li)(li)設備(bei)用電(dian)(dian)(dian)(dian)氣(qi)裝備(bei)電(dian)(dian)(dian)(dian)線(xian)(xian)電(dian)(dian)(dian)(dian)纜(lan)(lan)(lan)等。
(2)、信息傳輸系統
用于信息(xi)傳輸系統的電線(xian)電纜(lan)(lan)主要(yao)有市話(hua)電纜(lan)(lan)、電視電纜(lan)(lan)、電子(zi)線(xian)纜(lan)(lan)、射頻電纜(lan)(lan)、光纖纜(lan)(lan)、數據電纜(lan)(lan)、電磁線(xian)、電力通訊(xun)或其他復(fu)合電纜(lan)(lan)等(deng)。
(3)、機械設備(bei)、儀(yi)器(qi)儀(yi)表系統
此部分除架空裸電(dian)(dian)(dian)(dian)線外(wai)幾乎其他(ta)所有產品均(jun)有應用,但主要是(shi)電(dian)(dian)(dian)(dian)力電(dian)(dian)(dian)(dian)纜、電(dian)(dian)(dian)(dian)磁線、數據電(dian)(dian)(dian)(dian)纜、儀器儀表線纜等。
31、電(dian)線電(dian)纜產品主要分(fen)為(wei)五(wu)大類:
(1)、裸電線及裸導(dao)體(ti)制品 本(ben)類產品的主(zhu)(zhu)要(yao)特征是:純的導(dao)體(ti)金屬,無絕(jue)緣(yuan)及護套層,如鋼(gang)芯鋁絞線、銅鋁匯流排、電力(li)機車線等;加工工藝(yi)主(zhu)(zhu)要(yao)是壓力(li)加工,如熔煉、壓延、拉制、絞合/緊壓絞合等;產品主(zhu)(zhu)要(yao)用在(zai)城郊、農村、用戶(hu)主(zhu)(zhu)線、開關(guan)柜等。
(2)、電力電纜(lan)本類產品(pin)主要特征(zheng)是:在(zai)導體外擠(繞)包絕(jue)(jue)緣(yuan)層(ceng)(ceng),如(ru)(ru)架(jia)空(kong)絕(jue)(jue)緣(yuan)電纜(lan),或幾芯絞合(he)(he)(對(dui)應電力系統的相線(xian)、零線(xian)和地(di)線(xian)),如(ru)(ru)二芯以上(shang)架(jia)空(kong)絕(jue)(jue)緣(yuan)電纜(lan),或再增加護套層(ceng)(ceng),如(ru)(ru)塑料/橡套電線(xian)電纜(lan)。主要的工藝技術(shu)有拉(la)制、絞合(he)(he)、絕(jue)(jue)緣(yuan)擠出(繞包)、成(cheng)纜(lan)、鎧裝、護層(ceng)(ceng)擠出等,各種產品(pin)的不同工序組合(he)(he)有一(yi)定區別。
產品(pin)主要(yao)用(yong)在發、配、輸(shu)、變(bian)、供電線路中的(de)強電電能傳(chuan)輸(shu),通過的(de)電流大(幾(ji)十安至幾(ji)千安)、電壓(ya)高(220V至500kV及以(yi)上)。
(3)、電氣(qi)裝備用(yong)電線(xian)(xian)電纜(lan)(lan)該類產品(pin)(pin)主要特征是:品(pin)(pin)種規格繁多(duo),應用(yong)范圍廣泛,使用(yong)電壓在1kV及以下較多(duo),面(mian)對特殊場合不斷(duan)衍生(sheng)新(xin)的(de)產品(pin)(pin),如耐火(huo)線(xian)(xian)纜(lan)(lan)、阻燃(ran)線(xian)(xian)纜(lan)(lan)、低煙(yan)(yan)無鹵(lu)/低煙(yan)(yan)低鹵(lu)線(xian)(xian)纜(lan)(lan)、防白(bai)蟻、防老鼠線(xian)(xian)纜(lan)(lan)、耐油/耐寒/耐溫/耐磨線(xian)(xian)纜(lan)(lan)、醫用(yong)/農用(yong)/礦用(yong)線(xian)(xian)纜(lan)(lan)、薄壁電線(xian)(xian)等。
(4)、通(tong)訊電(dian)纜(lan)(lan)及光纖(簡略介紹)隨(sui)著近二十多(duo)年來,通(tong)訊行業的飛速發(fa)展(zhan),產品也(ye)有驚(jing)人的發(fa)展(zhan)速度。從過去(qu)的簡單的電(dian)話電(dian)報(bao)線纜(lan)(lan)發(fa)展(zhan)到幾(ji)千對的話纜(lan)(lan)、同軸纜(lan)(lan)、光纜(lan)(lan)、數據電(dian)纜(lan)(lan),甚至組(zu)合通(tong)訊纜(lan)(lan)等。
該(gai)類產(chan)品結(jie)構尺寸通常較(jiao)小而均勻,制造精(jing)度要求高。
(5)、電磁(ci)線(繞組線)主要(yao)用于各(ge)種電機、儀器儀表等(deng)。
電(dian)(dian)線電(dian)(dian)纜的衍生/新產品
電線電纜的(de)(de)衍生(sheng)/新(xin)(xin)產品(pin)(pin)主(zhu)要(yao)是(shi)因應用(yong)場合(he)、應用(yong)要(yao)求(qiu)不同(tong)及裝(zhuang)備的(de)(de)方便性(xing)和降低裝(zhuang)備成本(ben)等的(de)(de)要(yao)求(qiu),而采用(yong)新(xin)(xin)材料(liao)、特殊材料(liao)、或改變產品(pin)(pin)結構、或提高(gao)工藝要(yao)求(qiu)、或將(jiang)不同(tong)品(pin)(pin)種(zhong)的(de)(de)產品(pin)(pin)進行組合(he)而產生(sheng)。
采用不同(tong)材料如(ru)阻(zu)燃線纜(lan)、低(di)(di)煙無(wu)鹵/低(di)(di)煙低(di)(di)鹵線纜(lan)、防白蟻、防老鼠線纜(lan)、耐油/耐寒/耐溫線纜(lan)等(deng);
改(gai)變產品結構如(ru):耐火(huo)電(dian)纜等;
提高工藝要求如:醫用線纜等;
組合產(chan)品如(ru):OPGW等;
方便安裝和降低(di)裝備(bei)成本(ben)如:預制分支電纜等。
32、母線(xian)裝置施工完,應進行哪些檢查(cha)?
答:應進(jin)行下列檢(jian)查:
(1)金屬(shu)構件的(de)加工、配制、焊(han)接(jie)螺接(jie)應(ying)符合(he)規定;
(2)各(ge)部螺栓(shuan)、墊圈、開口銷等零(ling)部件應齊全可靠;
(3)母線配制(zhi)及安裝架應符(fu)合規定,相(xiang)間及對地(di)電氣(qi)距(ju)離(li)符(fu)合要求;
(4)瓷件(jian)、鐵件(jian)及膠合處應完整,充油套管應無(wu)滲油,油位正常;
(5)油漆完(wan)整(zheng),相(xiang)色(se)正確,接地(di)良好。
33、在35kv及(ji)以下電力電纜接頭(tou)中,改(gai)善(shan)其(qi)護套斷開處(chu)電場分布的(de)方法(fa)有幾(ji)種(zhong)(請列出(chu)五(wu)種(zhong)),并簡述其(qi)方法(fa)。
答:(1)脹喇叭口:在鉛包割斷處把鉛包邊(bian)緣撬起,成喇叭狀(zhuang),其(qi)邊(bian)緣應光滑、圓整、對(dui)稱。
(2)預留統包絕緣:在鉛包切(qie)口至電(dian)纜芯線分開點(dian)之間留有一(yi)段統包絕緣紙。
(3)切(qie)除半導電紙:將半導電紙切(qie)除到喇叭口以下。
(4)包繞應力錐:用絕緣包帶和導電(dian)金屬材料包成錐形,人為地將(jiang)屏蔽層擴大,以改善電(dian)場分布(bu)。
(5)等電(dian)位法:對(dui)于干(gan)包型或(huo)交聯聚乙烯電(dian)纜頭,在(zai)各線芯(xin)概(gai)況絕緣表面上包一段金屬(shu)帶,并(bing)將其(qi)連接(jie)在(zai)一起(qi)。
(6)裝設(she)應(ying)力控制管(guan):對于35kv及發下熱縮管(guan)電纜頭,首先(xian)從(cong)線(xian)芯(xin)銅屏蔽層(ceng)末端方(fang)向經(jing)半導體(ti)帶至線(xian)芯(xin)絕緣概況包繞2層(ceng)半導體(ti)帶,然(ran)后將相應(ying)規格折(zhe)應(ying)力管(guan),套在銅屏蔽的末端處,熱縮成形。
34、電纜支(zhi)架的加工應符合哪些要(yao)求?
答(da):(1)鋼(gang)材應(ying)(ying)平直(zhi),無明顯扭曲,下料誤差應(ying)(ying)在(zai)5mm范圍內,切口應(ying)(ying)無卷邊(bian),毛剌(la);
(2)支(zhi)架應(ying)焊(han)接牢固(gu),無顯蓍(shi)變形,各橫撐間的垂直凈距(ju)與設計(ji)偏差不應(ying)大于5mm;
(3)金屬(shu)支架(jia)必須(xu)進行(xing)防(fang)腐處理,位于濕熱、鹽、霧以及有(you)化學腐蝕地(di)區時(shi),應根據(ju)設(she)計(ji)作特殊的防(fang)腐處理。
35、列舉出你熟(shu)悉的電(dian)纜架。
答:拼焊式(shi)(shi)E型架、裝配(pei)式(shi)(shi)E型架、橋式(shi)(shi)電(dian)(dian)纜架、電(dian)(dian)纜托架、掛(gua)鉤式(shi)(shi)支架、單根電(dian)(dian)纜支架等。
36、敷設(she)電纜(lan)應滿足哪些要求(qiu)?
答(da):應滿足以(yi)下要求:
(1)安全運行方面,盡可能避免(mian)各(ge)種外(wai)來(lai)損(sun)壞,提高(gao)電纜線路的(de)供電可靠性;
(2)經濟方面(mian),從投資最(zui)省的方面(mian)考慮;
(3)施工方面,電纜線路(lu)的路(lu)徑(jing)必(bi)須便于(yu)旋工和投運后的維(wei)修。
37、制作電纜(lan)終端(duan)頭或中間(jian)接頭的絕(jue)緣材料有(you)哪些(xie)?
答:有絕緣(yuan)膠、絕緣(yuan)帶(dai)、絕緣(yuan)管(guan)、絕緣(yuan)手套、絕緣(yuan)樹脂等。
38、簡(jian)述(shu)電(dian)纜(lan)頭制作(zuo)的一般操(cao)作(zuo)程序(xu)。答:(1)制作(zuo)前(qian)的準備:包括○1閱讀(du)安裝說(shuo)明(ming)書(shu);○2察看現場;○3備料;○4電(dian)纜(lan)試潮;○5制作(zuo)前(qian)測試等。
(2)接頭(tou)的(de)制作過(guo)程:包括○1割斷多余(yu)電纜;○2電纜保護層的(de)剝(bo)切;○3導體連(lian)接;○4包繞絕緣(或收(shou)縮(suo)管材);○5安裝接頭(tou)外殼;○6灌(guan)注絕緣劑;○7進(jin)行(xing)密封處(chu)理等。
(3)制(zhi)作后電(dian)氣測試。
39、電纜保護管的加工應符合哪(na)些要求(qiu)?
答:(1)管(guan)口(kou)應*剌(la)和尖(jian)銳楞(leng)角(jiao),管(guan)口(kou)宜(yi)做成喇叭形。
(2)電纜(lan)管在彎制后,不應有裂縫和顯(xian)著的(de)凹癟現象,其彎扁程度不宜大于管子外徑(jing)10%;電纜(lan)管的(de)彎曲(qu)半(ban)徑(jing)不應小于所穿入(ru)電纜(lan)的(de)最小允許彎曲(qu)半(ban)徑(jing)。
(3)金(jin)屬管應(ying)(ying)在外表涂(tu)防腐漆或瀝表,鍍鋅(xin)(xin)管鋅(xin)(xin)層剝落處也(ye)應(ying)(ying)涂(tu)以防腐漆。
40、電纜的排列符(fu)合哪(na)些要求?答:(1)電力電纜和(he)控(kong)纜不應配置(zhi)在同一層支架上(shang)。
(2)高、低壓電(dian)纜(lan),強、弱電(dian)控纜(lan)應按須序分層(ceng)配(pei)置(zhi),一般情況宜(yi)由上(shang)而下,但在(zai)含(han)有35kv以上(shang)高壓電(dian)纜(lan)引入(ru)柜(ju)盤時,為滿足彎曲半徑,可由下面(mian)上(shang)配(pei)置(zhi)。
41、電纜溝(gou)內(nei)敷設電纜的(de)方(fang)法是什么?
答:在電(dian)(dian)纜溝(gou)內(nei)敷設(she)(she)電(dian)(dian)纜的方(fang)法(fa)與直埋(mai)電(dian)(dian)纜的敷設(she)(she)方(fang)法(fa)相(xiang)仿,一(yi)般可將滑輪放在溝(gou)內(nei),施(shi)放完畢,將電(dian)(dian)纜放于(yu)溝(gou)底或(huo)支架上,并在電(dian)(dian)纜上綁扎(zha)電(dian)(dian)纜標牌。
42、電(dian)纜敷設(she)的常用(yong)設(she)備有哪(na)些?
答:(1)空氣壓縮機(ji),主要用來破壞路(lu)面,為(wei)以后(hou)敷設(she)電纜作準(zhun)備;
(2)電(dian)(dian)動(dong)卷揚(yang)機(ji)或電(dian)(dian)纜牽引機(ji),主要用來拖電(dian)(dian)纜;
(3)電纜(lan)輸送機(ji),配(pei)合牽引(yin)機(ji)使用來克服巨大的摩擦(ca)力,減(jian)輕對電纜(lan)的損壞(huai);
(4)電纜盤放線(xian)支架;
(5)滾輪裝置;
(6)防捻(nian) ,減鋼絲繩出現的扭曲;
(7)電(dian)纜盤(pan)制(zhi)動(dong)裝(zhuang)置;
(8)張(zhang)力計。
43、電纜(lan)溝(gou)中支(zhi)(zhi)架安裝(zhuang)距離的(de)要求如何(he)?答:電纜(lan)固定(ding)于電纜(lan)溝(gou)和隧道的(de)墻上,水平裝(zhuang)置時,當電纜(lan)外(wai)徑(jing)等(deng)于或小于50mm時應(ying)每隔(ge)1m加(jia)(jia)一支(zhi)(zhi)撐(cheng);外(wai)徑(jing)大于50mm的(de)電纜(lan)每隔(ge)0.6m加(jia)(jia)一支(zhi)(zhi)撐(cheng);排成三角形的(de)單電纜(lan),每隔(ge)1m應(ying)用(yong)綁帶(dai)扎牢,垂(chui)直裝(zhuang)置時,每隔(ge)1~1.5m加(jia)(jia)以固定(ding)。
44、如何處理電力電纜(lan)與控制電纜(lan)在同一(yi)托架的安(an)裝?
答:電(dian)力電(dian)纜(lan)與控(kong)制電(dian)纜(lan)一(yi)(yi)般不應敷設在同一(yi)(yi)托架內,當電(dian)纜(lan)較少而將控(kong)纜(lan)與電(dian)力電(dian)纜(lan)敷設在同一(yi)(yi)托架內時,應用(yong)隔板隔開。
45、電(dian)纜(lan)隧道內如何(he)裝設接地線(xian)?
答:隧道和(he)溝的全長(chang)應裝(zhuang)設連(lian)續的接(jie)地線,接(jie)地線應和(he)所有的支(zhi)架相連(lian),兩頭和(he)接(jie)地極(ji)連(lian)通。接(jie)地線的規格應符合設計要(yao)求(qiu)。電纜鉛包和(he)鎧裝(zhuang)除了有絕緣(yuan)要(yao)求(qiu)外,應全部相互連(lian)接(jie)并(bing)和(he)接(jie)地線相連(lian),電纜架和(he)接(jie)地線均應涂防銹漆或鍍鋅。
46、對(dui)于電纜孔洞的防火封堵有何(he)要求?
答(da):對于較大的電(dian)纜貫穿(chuan)孔洞,如電(dian)纜貫穿(chuan)樓板處(chu)等,采用(yong)防火堵料(liao)(liao)(liao)封堵時(shi),應根(gen)據實際情(qing)況,先在電(dian)纜表面(mian)涂四至六層防火涂料(liao)(liao)(liao),長(chang)度自(zi)孔洞以下1.5m左右,再用(yong)耐火材料(liao)(liao)(liao)加工成具有(you)一(yi)定強度的板托(tuo)防火堵料(liao)(liao)(liao),保證封堵后牢固并(bing)便于更(geng)換電(dian)纜時(shi)拆裝,封堵密(mi)實無孔隙以有(you)效地堵煙堵火。
47、噴(pen)燈點火(huo)前應注意哪些檢(jian)查?
答:應進行(xing)下列(lie)各項檢(jian)查:
(1)打氣(qi)筒(tong)是否漏(lou)油或滲油,油桶及(ji)噴(pen)嘴處是否漏(lou)油、漏(lou)氣(qi);
(2)油(you)(you)桶內的(de)油(you)(you)量是否超過油(you)(you)桶容量的(de)3/4,加油(you)(you)的(de)螺絲塞是否擰(ning)緊。
48、使用(yong)噴燈應注意哪(na)些事項?
答:(1)噴燈(deng)更(geng)大 注油量為(wei)油筒容(rong)積的3/4;
(2)開始打氣壓力不要太大,點燃后火(huo)焰由(you)黃變藍即可使用;
(3)周圍不得有易燃物,空氣要流通;
(4)停用時(shi)先關閉(bi)調(diao)節開(kai)關,火熄后(hou),慢慢旋(xuan)松油孔蓋(gai)放氣,空氣放完后(hou),要要旋(xuan)松調(diao)節開(kai)關,完全冷卻(que)后(hou)再旋(xuan)松孔蓋(gai);
(5)煤油噴燈與(yu)汽油噴燈要分開使用。
49、手動油壓鉗有何(he)用途?如(ru)何(he)操作?
答(da):兩根導線的連(lian)接(jie)(jie)通(tong)常是(shi)將兩導線端穿(chuan)入(ru)相同材(cai)料制成的壓(ya)(ya)(ya)管(guan)中,用壓(ya)(ya)(ya)接(jie)(jie)鉗(qian)擠壓(ya)(ya)(ya)數個(ge)(ge)坑(keng),使導線連(lian)接(jie)(jie)在(zai)一(yi)起,壓(ya)(ya)(ya)接(jie)(jie)時,手(shou)柄向(xiang)(xiang)上抬起時,柱(zhu)塞(sai)(sai)向(xiang)(xiang)外移(yi)(yi)動(dong),進(jin)油(you)閥下腔產生真空,油(you)箱內的油(you)進(jin)入(ru)柱(zhu)塞(sai)(sai)腔。手(shou)柄下壓(ya)(ya)(ya)時,柱(zhu)塞(sai)(sai)向(xiang)(xiang)內移(yi)(yi)動(dong),油(you)受壓(ya)(ya)(ya)后,使進(jin)油(you)閥關閉,打(da)開(kai)出油(you)閥,使油(you)壓(ya)(ya)(ya)進(jin)入(ru)液壓(ya)(ya)(ya)缸,推(tui)動(dong)活(huo)塞(sai)(sai)和陽模,陽、陰模之間放(fang)有壓(ya)(ya)(ya)接(jie)(jie)管(guan),當壓(ya)(ya)(ya)接(jie)(jie)被(bei)擠壓(ya)(ya)(ya)的坑(keng)深到一(yi)定值時,開(kai)啟回油(you)閥,活(huo)塞(sai)(sai)自(zi)動(dong)返回,壓(ya)(ya)(ya)完一(yi)個(ge)(ge)坑(keng)后,移(yi)(yi)動(dong)壓(ya)(ya)(ya)鉗(qian),再壓(ya)(ya)(ya)下一(yi)個(ge)(ge)。
50、常用(yong)低壓電力電纜按絕緣和保護層的不同(tong),主要可(ke)分為哪(na)幾類?
答(da):(1)油浸(jin)紙絕緣鉛包(或鋁(lv)包)電力電纜;
(2)不(bu)滴流油浸紙絕緣電(dian)力電(dian)纜(lan);
(3)聚氯(lv)乙烯絕緣聚氯(lv)乙烯護套電力電纜;
(4)交(jiao)聯聚(ju)氯乙烯絕(jue)緣聚(ju)乙烯護(hu)套電(dian)(dian)力(li)電(dian)(dian)纜;
(5)交(jiao)聯聚氯乙烯絕緣聚氯乙烯護套(tao)電(dian)力電(dian)纜;
(6)橡皮絕緣電(dian)力電(dian)纜。
51、常用(yong)絕緣材料的類別哪些?舉例(li)說明?
答:(1)無機絕緣材料:有云母(mu)、石棉、大(da)理石、瓷器(qi)、玻(bo)璃(li)等(deng);
(2)有(you)(you)機絕緣材料:有(you)(you)樹脂、橡膠、紙、麻、棉紗等;
(3)混合絕緣材料(liao)(liao):用以上(shang)絕緣材料(liao)(liao)加工(gong)而成型的名種絕緣材料(liao)(liao)。
52、在哪(na)種情(qing)況下采用(yong)排管敷(fu)設(she)?有什么優點?
答:排管敷(fu)設一般用在(zai)與其他建(jian)(jian)筑(zhu)物(wu)、公路(lu)或鐵(tie)路(lu)相(xiang)交叉的地方,有時也在(zai)建(jian)(jian)筑(zhu)物(wu)密集(ji)區內采用。主要(yao)優(you)點(dian)是占地少,能承受大的荷重,電纜(lan)相(xiang)互間(jian)互不影響,比較安全。
53、何(he)謂電纜(lan)長期允許載(zai)流量?
答:電纜(lan)長期允(yun)許(xu)載(zai)流(liu)量是指在(zai)電纜(lan)內通過(guo)規(gui)定(ding)電流(liu)時(shi),在(zai)熱穩定(ding)后,電纜(lan)導體達到(dao)長期允(yun)許(xu)工作溫度時(shi)的電流(liu)數(shu)值。
54、決定(ding)電纜長期允許載流量的(de)因素有哪些?
答:有以(yi)下三個因素決(jue)定:
(1)電纜(lan)的長期容許工作溫度;
(2)電纜(lan)本身的散熱(re)性能;
(3)電纜裝置(zhi)情況及(ji)周(zhou)圍環境的(de)散熱條件。
55、電纜的敷設方式(shi)有(you)幾種(zhong)?
答:有(you)以下幾種(zhong):
(1)直埋(mai)在地下;
(2)安裝在電纜溝內;
(3)安裝在(zai)地下隧道內(nei);
(4)安裝在(zai)建筑(zhu)物內(nei)部墻上或天棚上;
(5)安裝在橋架(jia)上(shang);
(6)敷設在排(pai)管內;
(7)敷設在水底。
56、如何進行電纜管的(de)連接工(gong)作?
答:電纜管(guan)連(lian)接(jie)(jie)(jie)時(shi),必(bi)須用(yong)扣和管(guan)接(jie)(jie)(jie)頭(tou)連(lian)接(jie)(jie)(jie),如采(cai)用(yong)焊(han)接(jie)(jie)(jie)時(shi),不(bu)能直接(jie)(jie)(jie)對(dui)焊(han),連(lian)接(jie)(jie)(jie)處(chu)要套上一段粗管(guan)再進行焊(han)接(jie)(jie)(jie),以免焊(han)渣掉(diao)入管(guan)內(nei)。
57、制作電(dian)纜頭時,對上下(xia)扳彎電(dian)纜芯線(xian)有何要求?
答:扳(ban)彎(wan)線(xian)芯時(shi)(shi),不得損傷紙絕緣(yuan),芯線(xian)的(de)(de)彎(wan)曲(qu)半(ban)徑不得小于(yu)電纜線(xian)芯的(de)(de)10倍。制作(zuo)時(shi)(shi)要特(te)別小心,應(ying)使線(xian)芯彎(wan)曲(qu)部分均勻受(shou)力,否則極(ji)易損傷絕緣(yuan)紙。
58、簡(jian)述塑(su)料電纜的熱收(shou)縮密封法(fa)。
答(da):熱(re)(re)縮(suo)(suo)法適(shi)用(yong)(yong)于(yu)中(zhong)、低壓橡、塑電纜接頭和終端頭的(de)密封,也(ye)可適(shi)用(yong)(yong)于(yu)不滴流和黏(nian)性浸漬絕緣電纜。采用(yong)(yong)交聯(lian)聚乙烯型(xing)和硅橡膠型(xing)兩大類遇(yu)熱(re)(re)后(hou)能均勻收(shou)縮(suo)(suo)的(de)熱(re)(re)收(shou)縮(suo)(suo)管。將這種管材(cai)套于(yu)預(yu)定的(de)粘合密封部位,并(bing)在粘和部位涂上熱(re)(re)熔膠,當加熱(re)(re)到一(yi)定溫(wen)度后(hou),熱(re)(re)縮(suo)(suo)管將收(shou)縮(suo)(suo),同時熱(re)(re)熔膠熔化(hua),待(dai)自(zi)然(ran)冷卻后(hou)即形(xing)成一(yi)道良好的(de)密封封層。
59、用電(dian)動彎管機彎制電(dian)纜保護管時應注意什么?
答:(1)彎管機應由了(le)解其性(xing)能(neng)并熟悉(xi)操作知(zhi)識的人員操作;
(2)使用前必(bi)須進行(xing)(xing)檢(jian)查,按(an)鈕(niu)、操作把手、行(xing)(xing)程(cheng)開(kai)關(guan)應完(wan)好,彎管機必(bi)須可靠接地;
(3)選(xuan)用(yong)符合(he)要(yao)求的模具,確定(ding)好所需(xu)要(yao)的彎曲半(ban)徑;
(4)施(shi)工場地周圍,應有(you)充足的活動范圍;
(5)使用(yong)時待空轉正(zheng)常(chang)后,方可帶負(fu)荷工作,運行中,嚴禁用(yong)手腳(jiao)接觸其轉動(dong)部分;
(6)工作完畢應(ying)及時停(ting)電,釋(shi)放(fang)油壓。
60、電纜(lan)清(qing)冊的內(nei)容及電纜(lan)編號(hao)的含(han)義是什么?
答:電纜(lan)清冊是施放(fang)電纜(lan)和指導施工的依據(ju),運行維護的檔案資料(liao)。應列入每(mei)根(gen)(gen)電纜(lan)的編號(hao)、起始點、型號(hao)、規格、長(chang)度,并分類統計出(chu)總長(chang)度,控纜(lan)還應列出(chu)每(mei)根(gen)(gen)電纜(lan)的備用芯。
電纜編號是識別(bie)電纜的(de)標志,故要求全廠編號不重(zhong)復,并且有一定的(de)含義和規律,能表達電纜的(de)特征(zheng)。
61、電(dian)纜(lan)目(mu)前采用的敷設(she)方法(fa)可分為(wei)幾(ji)類?
答:(1)人(ren)工敷設(she)(she),即采用人(ren)海(hai)戰術,在一人(ren)或多(duo)人(ren)協調指揮下,按規定進行敷設(she)(she);
(2)機械化敷設,即采(cai)用滾輪、牽引器、輸送機,通過(guo)一同步電源進行控(kong)制(zhi),比較安全(quan);
(3)人工和(he)機(ji)械(xie)相結合,有些現場由于轉彎較(jiao)多,施工難(nan)度大(da),全用機(ji)械(xie)較(jiao)困(kun)難(nan),所以采用此法。
62、控制二次回路接線(xian)應(ying)符合(he)哪些要(yao)求(qiu)?
答:(1)按圖(tu)施工(gong)接(jie)線正(zheng)確;
(2)導線的電氣連(lian)接應牢固可靠;
(3)盤柜內的(de)導(dao)線不應有接頭(tou),導(dao)線芯(xin)線應無損傷;
(4)電纜(lan)芯線端(duan)部應(ying)標明其回路編(bian)號,編(bian)號應(ying)正確,字跡(ji)清(qing)晰且不(bu)易(yi)脫色(se);
(5)配線(xian)應整齊(qi)、清晰(xi)、美(mei)觀,導線(xian)絕(jue)緣應良好、無(wu)損;
(6)每個接(jie)線端子(zi)的每側接(jie)線宜為一(yi)根,最(zui)多不得超過兩(liang)根。
63、電纜排管(guan)有何要求(qiu)?
答:(1)排(pai)管頂(ding)部至地(di)面距(ju)離(li),在(zai)廠房內(nei)為0.2m,人(ren)行道下為0.5m,一般地(di)區為0.7m;
(2)在變更方向及分支處均應(ying)裝置排(pai)管井(jing)坑(keng),長度超過30mm時也應(ying)加設(she)井(jing)坑(keng);
(3)井坑(keng)深度不小于(yu)0.8m,人孔(kong)直徑不小于(yu)0.7mm;
(4)排管應有傾(qing)向井(jing)坑0.5%~1%的排水坡度。
64、對于電纜導體連(lian)接點的電阻有何要求?
答:要求連接(jie)點的電(dian)阻小而(er)且穩定,連接(jie)點的電(dian)阻與相(xiang)同長(chang)度、相(xiang)同截面的導體之比(bi)值(zhi),對于(yu)(yu)新安裝(zhuang)的終(zhong)端頭(tou)和(he)中(zhong)間(jian)頭(tou),應不大于(yu)(yu)1;對于(yu)(yu)運(yun)行中(zhong)的終(zhong)端頭(tou)和(he)中(zhong)間(jian)頭(tou)這個比(bi)值(zhi)不應大于(yu)(yu)1.2。
65、電纜接頭和中間(jian)頭的(de)設計應滿足哪些要求?
答(da):應滿足(zu)的要求有:
(1)耐壓強度高,導體連接好;
(2)機械強度大,介質(zhi)損失小;
(3)結構簡單,密封性(xing)強。
66、什么是(shi)電纜故障?有幾種常見的(de)類型?
答:電纜(lan)(lan)故(gu)障(zhang)(zhang)是指電纜(lan)(lan)在預防性試驗時發生絕(jue)緣擊穿或在運行中(zhong),因(yin)絕(jue)緣擊穿、導線燒斷等而迫(po)使(shi)電纜(lan)(lan)線路停電的故(gu)障(zhang)(zhang)。常見的故(gu)障(zhang)(zhang)有(you)接地故(gu)障(zhang)(zhang)、短(duan)路故(gu)障(zhang)(zhang)、斷線故(gu)障(zhang)(zhang)、閃絡(luo)性故(gu)障(zhang)(zhang)和混合(he)型故(gu)障(zhang)(zhang)等。
67、如何處(chu)理電纜(lan)線路的(de)單相接地故障?
答:電纜線路單相接地故(gu)障(zhang)一般(ban)(ban)來(lai)說,電纜導體的損傷(shang)只(zhi)是局部的,如果屬于(yu)機械損傷(shang),而故(gu)障(zhang)點(dian)附(fu)近的土壤(rang)又較(jiao)干燥時(shi),一般(ban)(ban)可進行(xing)局部修理,加添一只(zhi)假(jia)接頭,即(ji)不(bu)將電纜芯鋸斷,僅將故(gu)障(zhang)點(dian)絕緣加強后密(mi)封(feng)即(ji)可。
68、電(dian)力電(dian)纜(lan)在敷(fu)設前(qian)應(ying)進行哪些試驗和檢查?
答:敷設前(qian)應檢查電(dian)(dian)纜的型號、規格及(ji)長度是否(fou)符合要求,是否(fou)有外力(li)損傷,低(di)壓電(dian)(dian)纜用1000V兆歐(ou)(ou)表遙測(ce)絕(jue)緣電(dian)(dian)阻(zu),阻(zu)值一般不低(di)于(yu)10MΩ,高壓電(dian)(dian)纜用2500V兆歐(ou)(ou)表搖測(ce)阻(zu)值一般不抵于(yu)400MΩ。
69、主廠房內敷設電纜時一般應注意什么?
答(da):在主廠房內(nei)敷設電纜時一(yi)般應(ying)注意:
(1)凡(fan)引至(zhi)集控室的控制電纜(lan)宜架空敷設;
(2)6KV電纜宜用(yong)隧道或(huo)排管敷(fu)設,地下水位高處亦可架空或(huo)用(yong)排管敷(fu)設;
(3)380V電纜當(dang)兩(liang)端(duan)電纜在(zai)零(ling)米時(shi)(shi)宜用隧道、溝(gou)或(huo)排管,當(dang)一端(duan)設備在(zai)上(shang)、一端(duan)在(zai)下時(shi)(shi),可部(bu)分(fen)架空(kong)敷(fu)設,當(dang)地下水位較高時(shi)(shi),宜架空(kong)。
70、電力電纜的內屏蔽(bi)層與外(wai)屏蔽(bi)層各在什(shen)么部位?采用(yong)(yong)什(shen)么材料?有何作(zuo)用(yong)(yong)?
答(da):為(wei)了使絕緣層(ceng)(ceng)和電纜導(dao)體有(you)(you)較(jiao)好的接(jie)觸(chu),消除導(dao)體表(biao)面(mian)(mian)的不(bu)光滑引起的導(dao)體表(biao)面(mian)(mian)電場強度的增加,一(yi)(yi)般在導(dao)體表(biao)面(mian)(mian)包有(you)(you)金屬(shu)化紙或半導(dao)體紙帶的內(nei)屏蔽層(ceng)(ceng)。為(wei)了使絕緣層(ceng)(ceng)和金屬(shu)護(hu)套有(you)(you)較(jiao)好的接(jie)觸(chu),一(yi)(yi)般在絕緣層(ceng)(ceng)外表(biao)面(mian)(mian)包有(you)(you)外層(ceng)(ceng)屏蔽層(ceng)(ceng)。外屏層(ceng)(ceng)與內(nei)屏層(ceng)(ceng)的材料相同,有(you)(you)時還外扎銅(tong)帶或編(bian)織銅(tong)絲帶。
71、簡述(shu)環(huan)氧(yang)樹脂復合(he)物的構成及性(xing)能。
答:環(huan)氧樹脂(zhi)復合物由環(huan)氧樹脂(zhi)加(jia)入硬化(hua)劑、填充劑增(zeng)韌劑和稀釋劑組成。具有(you)以下性能:
(1)有足夠的機(ji)械強度;
(2)電氣(qi)性能(neng)優良(liang);
(3)電氣性能穩定(ding);
(4)與有色金(jin)屬有足夠的(de)黏附力;
(5)耐腐蝕性好;
(6)戶外使用時,耐(nai)雨、耐(nai)光、耐(nai)濕熱。
72、單芯電(dian)(dian)纜護套一(yi)端接(jie)地(di)方(fang)式中為什(shen)么(me)必(bi)須安裝一(yi)條沿電(dian)(dian)纜平行敷(fu)設的(de)回流線(xian)?
答:在金屬(shu)護套(tao)一端(duan)接地(di)(di)的電(dian)(dian)(dian)纜(lan)線(xian)路中(zhong),為確保護套(tao)中(zhong)的感應電(dian)(dian)(dian)壓(ya)不超過(guo)(guo)允許標(biao)準,必須安裝(zhuang)一條沿電(dian)(dian)(dian)纜(lan)線(xian)路平行(xing)敷(fu)設的導(dao)體,且(qie)導(dao)體的兩端(duan)接地(di)(di),這種導(dao)體稱為回(hui)流線(xian)。當發(fa)生(sheng)單(dan)相接地(di)(di)故障(zhang)時,接地(di)(di)短路電(dian)(dian)(dian)流可以通(tong)過(guo)(guo)回(hui)流線(xian)流回(hui)系統(tong)中(zhong)心點(dian),由于通(tong)過(guo)(guo)回(hui)流線(xian)的接地(di)(di)電(dian)(dian)(dian)流產生(sheng)的磁通(tong)抵消了一部分電(dian)(dian)(dian)纜(lan)導(dao)線(xian)接地(di)(di)電(dian)(dian)(dian)流所產生(sheng)的磁通(tong),因而可降低(di)短路故障(zhang)時護套(tao)的感應電(dian)(dian)(dian)壓(ya)。
73、電纜(lan)工程可劃分為(wei)幾個(ge)項目?
答:(1)工地運輸:包括(kuo)工程材料(liao)從倉庫(ku)到施(shi)工點的裝卸、運輸和空車回程。
(2)地方工(gong)程:包括路面開挖、隧(sui)、溝(gou)道施工(gong)等。
(3)敷(fu)設工程:包括敷(fu)設、中間頭(tou)制作、掀蓋板(ban)、埋管、校潮、牽引頭(tou)制作等(deng)。
(4)兩端(duan)工程:包(bao)括支、吊橋(qiao)架和(he)其基礎的制作安(an)裝(zhuang)(zhuang),終端(duan)頭制作,油(you)壓力和(he)信號裝(zhuang)(zhuang)置的安(an)裝(zhuang)(zhuang),名種電氣性能(neng)測試等。
(5)塞止(zhi)工(gong)程:包括充油電纜塞止(zhi)頭(tou)制作,供油箱(xiang)、自動排水及(ji)信號裝(zhuang)置的安(an)裝(zhuang)等。
(6)接(jie)(jie)地(di)工程:包括(kuo)絕緣接(jie)(jie)頭、換位箱、保護(hu)器(qi)、接(jie)(jie)地(di)箱安裝(zhuang)等(deng)。
74、電纜線(xian)路的驗(yan)收(shou)應進(jin)行哪(na)些檢查?
答:(1)電纜規格應符合規定,排列應整(zheng)齊,無損傷(shang),標牌齊全、正確、清晰;
(2)電纜的(de)固定彎(wan)曲半徑、有關距離及單芯電力電纜的(de)金屬護(hu)層的(de)接線應符合要求(qiu);
(3)電纜終端、中間(jian)頭不(bu)滲漏油,安裝(zhuang)牢固,充油電纜油壓及表計(ji)整定(ding)值應符合要求(qiu);
(4)接地良好;
(5)電纜終端相色正確,支架(jia)等(deng)的金屬(shu)部件油(you)漆完整;
(6)電纜溝及隧(sui)道內、橋架上應無(wu)雜物,蓋板齊全(quan)。
75、電纜線(xian)路正序阻抗測量過程中(zhong)有什么(me)要求?
答(da):電纜導(dao)體的(de)交流(liu)電阻(zu)和電纜三相(xiang)同感抗的(de)相(xiang)量和稱為正序(xu)阻(zu)抗。
電(dian)(dian)(dian)纜(lan)(lan)線(xian)路的(de)正序阻抗一般(ban)可在電(dian)(dian)(dian)纜(lan)(lan)盤上(shang)直接測量,測量時一般(ban)使用(yong)較(jiao)(jiao)低的(de)電(dian)(dian)(dian)壓(ya)(ya),因此,需要用(yong)降(jiang)壓(ya)(ya)變壓(ya)(ya)器進行降(jiang)壓(ya)(ya),降(jiang)壓(ya)(ya)器采(cai)用(yong)星形接線(xian),容量一般(ban)為10kVA以(yi)上(shang),有(you)較(jiao)(jiao)廣(guang)的(de)電(dian)(dian)(dian)壓(ya)(ya)調節范(fan)圍(wei),測量時交(jiao)流(liu)電(dian)(dian)(dian)源應(ying)比(bi)較(jiao)(jiao)穩定,以(yi)保證測量時電(dian)(dian)(dian)流(liu)達(da)到規定的(de)要求,實際電(dian)(dian)(dian)壓(ya)(ya)表(biao)(biao)的(de)讀數值(zhi)必須是(shi)電(dian)(dian)(dian)纜(lan)(lan)端的(de)電(dian)(dian)(dian)壓(ya)(ya),試(shi)驗(yan)電(dian)(dian)(dian)流(liu)更好 接近電(dian)(dian)(dian)纜(lan)(lan)長(chang)期允許(xu)載流(liu)量,測讀各表(biao)(biao)計的(de)數值(zhi)時,合上(shang)電(dian)(dian)(dian)流(liu)后(hou)同時讀取三個表(biao)(biao)的(de)數值(zhi)。
76、根據(ju)《電業生產(chan)安全(quan)規定》,電氣工作(zuo)人員必須具備的條(tiao)件是什么?
答:必須具備(bei)下列(lie)條件:
(1)經醫生(sheng)鑒定身體(ti)健康,無妨礙(ai)工作的病癥;
(2)具備(bei)必要的(de)電氣知識,按其職務和(he)工作性質掌握(wo)相(xiang)關(guan)的(de)規程、專業技(ji)術及安全操作技(ji)術,并經考試合格(ge);
(3)熟練掌握(wo)觸電急救方法。
77、電纜在運輸裝卸過(guo)程(cheng)中應(ying)注(zhu)意什么(me)?
答(da):(1)在(zai)運輸裝卸過程(cheng)中(zhong),不應使電(dian)(dian)纜(lan)及電(dian)(dian)纜(lan)盤受到損(sun)傷,嚴禁(jin)將電(dian)(dian)纜(lan)盤直接由車上(shang)推(tui)下,電(dian)(dian)纜(lan)般不應平(ping)放(fang)運輸,平(ping)放(fang)貯存。
(2)運輸或滾(gun)動電(dian)纜盤前,必須保證電(dian)纜盤牢固,電(dian)纜繞緊、充(chong)油(you)電(dian)纜至壓力油(you)箱間的油(you)管應固定,不得損(sun)傷,壓力油(you)箱應牢固,壓力指(zhi)示應符合要求。
78、電纜(lan)防火有(you)哪(na)些措(cuo)施?
答:(1)采用(yong)阻(zu)燃電纜;
(2)采用防火電纜托架;
(3)采用(yong)防火涂料;
(4)電(dian)纜隧道、夾(jia)層出口等處設置防(fang)火(huo)隔墻、防(fang)火(huo)擋板;
(5)架空電(dian)纜應避開油管道、防(fang)爆門(men),否則應有要取局部穿管或隔(ge)熱防(fang)火措施。
79、選(xuan)擇電力(li)電纜的截面應從哪幾個(ge)方面考慮?
答(da):應考慮如下幾個方(fang)面:
(1)電(dian)纜長期允(yun)許通過的工作電(dian)流;
(2)一(yi)旦短路(lu)時的熱(re)穩定性(xing);
(3)線路上的電(dian)壓降不能超出允(yun)許工作范(fan)圍。
80、電力電纜和架空線(xian)比較有(you)哪(na)些優點?
答:(1)運行(xing)可靠,由于安裝在地下等隱蔽處,受外力破壞小,發生故(gu)障(zhang)的(de)機會(hui)較少,供(gong)電安全,不會(hui)給人身造成危(wei)害;
(2)維護(hu)工作量小(xiao),不需頻(pin)繁(fan)的巡檢;
(3)不需架設(she)桿(gan)塔;
(4)有助于提高功率因數。