1、常用(yong)的電線、電纜按(an)用(yong)途(tu)分(fen)有(you)哪些種(zhong)類?
答:按用途(tu)可分為裸導線(xian)(xian)、絕緣電線(xian)(xian)、耐熱電線(xian)(xian)、屏蔽電線(xian)(xian)、電力電纜(lan)、控制電纜(lan)、通信電纜(lan)、射頻電纜(lan)等。
2、絕緣電線有哪(na)幾種?
答(da):常有的絕(jue)(jue)(jue)(jue)緣(yuan)(yuan)(yuan)(yuan)電線(xian)(xian)(xian)有以下幾種(zhong):聚(ju)(ju)氯(lv)(lv)(lv)乙烯(xi)(xi)絕(jue)(jue)(jue)(jue)緣(yuan)(yuan)(yuan)(yuan)電線(xian)(xian)(xian)、聚(ju)(ju)氯(lv)(lv)(lv)乙烯(xi)(xi)絕(jue)(jue)(jue)(jue)緣(yuan)(yuan)(yuan)(yuan)軟(ruan)線(xian)(xian)(xian)、丁腈聚(ju)(ju)氯(lv)(lv)(lv)乙烯(xi)(xi)混合物(wu)絕(jue)(jue)(jue)(jue)緣(yuan)(yuan)(yuan)(yuan)軟(ruan)線(xian)(xian)(xian)、橡皮絕(jue)(jue)(jue)(jue)緣(yuan)(yuan)(yuan)(yuan)電線(xian)(xian)(xian)、農用(yong)地下直(zhi)埋鋁(lv)芯塑料絕(jue)(jue)(jue)(jue)緣(yuan)(yuan)(yuan)(yuan)電線(xian)(xian)(xian)、橡皮絕(jue)(jue)(jue)(jue)緣(yuan)(yuan)(yuan)(yuan)棉紗紡織軟(ruan)線(xian)(xian)(xian)、聚(ju)(ju)氯(lv)(lv)(lv)乙烯(xi)(xi)絕(jue)(jue)(jue)(jue)緣(yuan)(yuan)(yuan)(yuan)尼(ni)龍護套電線(xian)(xian)(xian)、電力和照明用(yong)聚(ju)(ju)氯(lv)(lv)(lv)乙烯(xi)(xi)絕(jue)(jue)(jue)(jue)緣(yuan)(yuan)(yuan)(yuan)軟(ruan)線(xian)(xian)(xian)等。
3、電纜橋架適合于何種場合?
答:電纜(lan)橋架適用(yong)于一般工礦企業室內外架空(kong)敷設(she)(she)電力電纜(lan)、控制(zhi)電纜(lan),亦可用(yong)于電信、廣播電視等部(bu)門在(zai)室內外架設(she)(she)。
4、電纜附件有哪些?
答:常用的電(dian)附件有(you)電(dian)纜終端接線(xian)盒、電(dian)纜中間接線(xian)盒、連接管及接線(xian)端子、鋼(gang)板接線(xian)槽、電(dian)纜橋架等。
5、什么叫電(dian)纜(lan)中間接(jie)頭?
答:連接(jie)電(dian)纜(lan)(lan)與電(dian)纜(lan)(lan)的(de)導體、絕緣屏蔽層和保(bao)護層,以使電(dian)纜(lan)(lan)線路連接(jie)的(de)裝(zhuang)置,稱(cheng)為電(dian)纜(lan)(lan)中間接(jie)頭。
6、什么叫(jiao)電氣主接線?
答:電(dian)氣主接(jie)線是發(fa)電(dian)廠、變電(dian)所中(zhong)主要(yao)電(dian)氣設備(bei)和母線的連接(jie)方(fang)式,包括(kuo)主母線和廠用電(dian)系統(tong)按一定的功(gong)能要(yao)求的連接(jie)方(fang)式。
7、在選擇電(dian)(dian)力(li)電(dian)(dian)纜的截面時,應遵(zun)照哪些(xie)規(gui)定?
答:電(dian)(dian)力電(dian)(dian)纜(lan)的(de)(de)選擇應(ying)遵照(zhao)以(yi)下(xia)原則:(1)電(dian)(dian)纜(lan)的(de)(de)額定(ding)電(dian)(dian)壓要大(da)于(yu)或等(deng)于(yu)安(an)裝點供電(dian)(dian)系(xi)(xi)統(tong)的(de)(de)額定(ding)電(dian)(dian)壓;(2)電(dian)(dian)纜(lan)持續(xu)容許電(dian)(dian)流(liu)應(ying)等(deng)于(yu)或大(da)于(yu)供電(dian)(dian)負(fu)載的(de)(de)更大(da) 持續(xu)電(dian)(dian)流(liu);(3)線芯截(jie)面要滿(man)足供電(dian)(dian)系(xi)(xi)統(tong)短路時的(de)(de)穩定(ding)性的(de)(de)要求(qiu);(4)根據(ju)電(dian)(dian)纜(lan)長(chang)度(du)驗算電(dian)(dian)壓降是(shi)否(fou)符合要求(qiu);(5)線路末端的(de)(de)最小短路電(dian)(dian)流(liu)應(ying)能(neng)使保護裝置可靠的(de)(de)動作(zuo)。
8、交聯聚乙烯電纜(lan)和油紙電纜(lan)比較有哪(na)些優點?
答:(1)易安裝,因為它(ta)允(yun)(yun)許最小(xiao)彎(wan)曲半徑小(xiao)、且(qie)重量輕(qing);(2)不受線路落差*;(3)熱性能(neng)好(hao),允(yun)(yun)許工作溫(wen)度高、傳(chuan)輸(shu)容量大;(4)電纜(lan)附件簡(jian)單,均為干(gan)式結構(gou);(5)運行維護簡(jian)單,無漏油問題;(6)價格較低(di);(7)可靠性高、故(gu)障(zhang)率低(di);(8)制造工序少、工藝簡(jian)單,經濟效益顯著。
9、固定交(jiao)流單芯(xin)電(dian)纜的夾具有什么要求?為(wei)什么?
答:夾具應無(wu)鐵件(jian)構成閉(bi)合磁路,這是(shi)因為當電(dian)(dian)纜(lan)(lan)線芯通過(guo)電(dian)(dian)流時(shi),在其周圍(wei)產生(sheng)磁力線,磁力線與通過(guo)線芯的(de)電(dian)(dian)流大(da)小成正比,若(ruo)使(shi)用(yong)鐵件(jian)等(deng)導(dao)磁材料,根(gen)據電(dian)(dian)磁感應可知,將在鐵件(jian)中產生(sheng)渦流使(shi)電(dian)(dian)纜(lan)(lan)發熱(re),甚(shen)至燒壞電(dian)(dian)纜(lan)(lan)。所以不可使(shi)用(yong)鐵件(jian)作單芯交(jiao)流電(dian)(dian)纜(lan)(lan)的(de)固定夾具。
10、以下的(de)熱縮電纜頭的(de)附件的(de)更大 特點和(he)優點是什(shen)么?
答:熱(re)縮附件的(de)(de)更大(da) 特點(dian)是用應力管代替傳統的(de)(de)應力錐,它不僅簡(jian)化了(le)(le)施(shi)工(gong)(gong)工(gong)(gong)藝(yi),還縮小了(le)(le)接頭的(de)(de)終端(duan)的(de)(de)尺寸,安裝方便(bian),省時省工(gong)(gong),性能優(you)越,節約金屬。熱(re)縮電纜附件集(ji)灌注(zhu)式(shi)和干(gan)包(bao)式(shi)為(wei)一(yi)體,集(ji)合了(le)(le)這兩(liang)種附件的(de)(de)優(you)點(dian)。
11、電纜敷(fu)設前應進行哪些檢查(cha)工(gong)作?
答:(1)支架應齊全、油漆(qi)完(wan)整。(2)電(dian)(dian)(dian)(dian)纜(lan)型(xing)號、電(dian)(dian)(dian)(dian)壓(ya)、規格(ge)(ge)符合(he)(he)設計。(3)電(dian)(dian)(dian)(dian)纜(lan)絕緣良好,當對(dui)油紙電(dian)(dian)(dian)(dian)纜(lan)的密封(feng)有懷疑(yi)時,應進行(xing)受潮(chao)判斷;直埋(mai)電(dian)(dian)(dian)(dian)纜(lan)與小(xiao)底(di)電(dian)(dian)(dian)(dian)纜(lan)應經直流耐(nai)壓(ya)試難合(he)(he)格(ge)(ge);充油電(dian)(dian)(dian)(dian)纜(lan)的油樣應試驗(yan)合(he)(he)格(ge)(ge)。(4)充油電(dian)(dian)(dian)(dian)纜(lan)的油壓(ya)不宜(yi)低于1.47MPa。
11、交(jiao)聯熱收縮電(dian)纜(lan)附件有哪些優點?
答:這(zhe)是一種新型材(cai)料(liao),它與現在(zai)其他類(lei)型附件(jian)比較具(ju)有電氣性能(neng)優越、體(ti)積(ji)小(xiao)、質量小(xiao)、安裝簡便、材(cai)料(liao)配套(tao)等(deng)優點,另外還(huan)具(ju)有耐氣候、抗污(wu)穢性、阻燃自(zi)熄等(deng)能(neng)力。
12、對油紙(zhi)絕(jue)緣(yuan)電力電纜密封有懷疑時,如何用較簡(jian)單的辦法檢查電纜絕(jue)緣(yuan)紙(zhi)是否受潮?
答:把電(dian)纜絕(jue)緣(yuan)紙點燃或放入150℃左右的(de)電(dian)纜油中(zhong)檢查(cha),無“嘶(si)嘶(si)”聲或白色(se)泡沫出現,說明未受潮。
13、電(dian)纜標志牌應注明什么內(nei)容(rong)?編寫有何要求?
答(da):標志牌上應(ying)注明電纜線路設計編號(hao)、電纜型號(hao)、規格及始點,并聯使用的電纜應(ying)有順序號(hao)。要求字(zi)跡清晰、不易脫落。
14、直(zhi)埋電(dian)纜的(de)方位(wei)標(biao)志應設(she)置在哪(na)些位(wei)置?
答:在電纜(lan)兩端,電纜(lan)直線段50~100m處(chu)電纜(lan)接(jie)頭幾電纜(lan)改變方向的彎角(jiao)處(chu)。
15、制作電纜接頭用的黃臘(la)綢帶、黑玻璃漆帶、無堿玻璃絲帶等,施工前如何進行排(pai)潮處(chu)理(li)?
答:(1)恒溫干燥法:將絕(jue)緣帶卷成直(zhi)徑為25~30mm小卷,放入(ru)110~120℃恒溫干燥箱內烘4~5h,冷卻干取(qu)出,放入(ru)干燥的密(mi)封筒內。(2)油(you)(you)(you)浸排潮法:將絕(jue)緣帶小卷放入(ru)恒溫在120~130℃的電纜(lan)油(you)(you)(you)中(zhong),離(li)鍋(guo)底保持30mm距離(li),經一(yi)定時間后(hou)油(you)(you)(you)面(mian)不再產生泡(pao)沫后(hou)取(qu)出,裝入(ru)貯有(you)電纜(lan)油(you)(you)(you)的桶中(zhong),油(you)(you)(you)位應超過所(suo)有(you)裝入(ru)的物體(ti)并將其密(mi)封。
16、電纜外護層(ceng)的作(zuo)用是(shi)什么?
答(da):保護內(nei)護層不受(shou)機械損傷和化學(xue)腐(fu)蝕,增強(qiang)機械強(qiang)度。
17、室外電纜溝應符(fu)合(he)哪(na)些(xie)要求?
答:電(dian)纜(lan)溝上(shang)部應比(bi)地面稍高,加蓋(gai)用(yong)混凝土制(zhi)作的(de)蓋(gai)板,電(dian)纜(lan)應平敷在支架上(shang),有(you)良好的(de)排水管。
18、電纜內護層的作用是什么?
答;使絕緣層不(bu)會(hui)與水(shui)、空氣或其他物體接觸,防止(zhi)絕緣受(shou)潮和絕緣層不(bu)受(shou)機械(xie)傷(shang)害。
19、使用(yong)鋼絲鉗(qian)時應注(zhu)意些什么?
答:使用(yong)(yong)前,一(yi)定要檢查絕(jue)緣柄的絕(jue)緣是否完好無損,使用(yong)(yong)時不可用(yong)(yong)鋼絲鉗(qian)剪切超過(guo)規格所允許的金屬線材,并禁止用(yong)(yong)鋼絲鉗(qian)代替錘子敲打工具,以(yi)免(mian)損壞。
20、什么叫絕(jue)緣強度?
答:絕緣(yuan)(yuan)物質在電(dian)(dian)場(chang)中,當電(dian)(dian)場(chang)強度(du)增(zeng)大到某一極(ji)限(xian)時就會被擊穿,這(zhe)個導致絕緣(yuan)(yuan)擊穿的電(dian)(dian)場(chang)強度(du)稱為絕緣(yuan)(yuan)強度(du)。
22、對電纜導體連(lian)接(jie)點的(de)機械(xie)強度有何要求?
答:連(lian)接(jie)點(dian)的(de)機(ji)械強(qiang)度(du),一般(ban)低于(yu)電纜導體(ti)本身的(de)抗(kang)拉強(qiang)度(du),對于(yu)固定敷(fu)設的(de)電力電纜,其連(lian)接(jie)點(dian)的(de)抗(kang)拉強(qiang)度(du)要求不低于(yu)導體(ti)本身抗(kang)拉強(qiang)度(du)的(de)60%。
23、電力電纜的絕緣層材料應具(ju)備哪些主要性能(neng)?
答(da);應具(ju)備下列(lie)主要性能:(1)高的(de)擊穿強度;(2)低的(de)介質損(sun)耗(hao);(3)相當高的(de)絕緣電阻;(4)優良的(de)耐(nai)放(fang)電性能;(5)具(ju)有一定(ding)的(de)柔軟性和機械強度;(6)絕緣性能長期穩定(ding)。
24、機(ji)械敷設電纜時,牽(qian)引強度有(you)何規定(ding)?
答:對(dui)于(yu)(yu)銅芯(xin)電(dian)纜(lan),當牽(qian)引(yin)(yin)頭部時,允許牽(qian)引(yin)(yin)強(qiang)度(du)為70N/cm;對(dui)于(yu)(yu)鋁芯(xin)電(dian)纜(lan),當牽(qian)引(yin)(yin)頭部時,允許牽(qian)引(yin)(yin)強(qiang)度(du)為40N/cm;若利用鋼絲網套牽(qian)引(yin)(yin)時,鉛(qian)護套電(dian)纜(lan)允許強(qiang)度(du)為10N/cm;鉛(qian)護套電(dian)纜(lan)為40N/cm。
25、對電(dian)纜(lan)保護(hu)管有何規定?
答:(1)電(dian)纜需(xu)要穿保(bao)護管(guan)敷設(she)時(shi),管(guan)子(zi)內(nei)徑(jing)不(bu)應(ying)小(xiao)于(yu)電(dian)纜外徑(jing)的1.5倍(bei),混凝土管(guan)、陶土管(guan)、石(shi)棉(mian)、水泥(ni)管(guan)的內(nei)徑(jing)不(bu)應(ying)小(xiao)于(yu)100mm;
(2)電纜管的(de)彎曲半徑應符合所穿入電纜彎曲半徑的(de)規定;
(3)每(mei)根管子最多(duo)不應(ying)超過三個彎頭,直角(jiao)彎不應(ying)多(duo)于2個。
26、如何測量電纜護套(tao)的外徑?
答:在(zai)護(hu)套(tao)圓(yuan)周上均勻分布的(de)五(wu)點(dian)處,測(ce)量(liang)護(hu)套(tao)外徑(jing)和其(qi)平(ping)均值,其(qi)平(ping)均外徑(jing)既為護(hu)套(tao)的(de)外徑(jing)。
27、不同(tong)截面的銅芯電(dian)纜如何連接?
答:不同截面(mian)的銅芯電纜連(lian)接(jie)(jie),可(ke)采用開口弱背銅接(jie)(jie)管,以錫焊法連(lian)接(jie)(jie),也(ye)可(ke)用純銅棒按不同的截面(mian)要求連(lian)接(jie)(jie)成銅接(jie)(jie)管,以壓接(jie)(jie)法連(lian)接(jie)(jie)。
28、簡(jian)述(shu)10KV交聯電纜熱(re)縮式制作戶內(nei)終端頭的過程?
答;(1)準備階段:檢查(cha)(cha)熱(re)縮電(dian)(dian)纜(lan)附(fu)件(jian)是否(fou)齊備,型(xing)號是否(fou)相配,檢查(cha)(cha)并確認電(dian)(dian)纜(lan)有無潮(chao)氣后,檢查(cha)(cha)電(dian)(dian)纜(lan)。
(2)切除多余(yu)電(dian)纜,根據現(xian)場情況決定電(dian)纜長度(du)。
(3)剝除護(hu)層(ceng)。
(4)焊(han)接(jie)(jie)接(jie)(jie)地(di)線,將接(jie)(jie)地(di)線焊(han)接(jie)(jie)在鋼帶上(shang)。
(5)填充三叉口(kou)及繞(rao)包密(mi)封膠。
(6)安裝三芯分(fen)支護套,將護套套入根(gen)部,從(cong)中部開始收(shou)縮,先往根(gen)部,再往指部。
(7)剝銅 帶和外半(ban)導(dao)(dao)電層,剝切三(san)芯(xin)分支套(tao)口(kou)20mm以上的(de)銅帶,嚴(yan)禁損(sun)傷主絕緣,清除干凈半(ban)導(dao)(dao)電層。
(8)安裝應(ying)力管(guan),管(guan)口端部(bu)分支套(tao)對(dui)接后熱縮。
(9)安裝接(jie)線端(duan)子。
(10)安(an)裝絕緣管。
(11)安裝密封管。
(12)核相后安裝相色管。
29、戶(hu)內、戶(hu)外預制式(shi)終端安裝步驟有哪些?
答:(1) 將電纜按預定(ding)位置就位、固(gu)定(ding)、清(qing)潔(jie)表(biao)面,參照(zhao)說明書剝除外護套(tao),如有特殊(shu)需(xu)要,外護套(tao)剝切(qie)長度(du)可(ke)調(diao)整,分別由銅帶(dai)、外護套(tao)鎧裝(zhuang)引出2組地線(xian)。
(2) 由外護套(tao)口(kou)向(xiang)上(shang)量取(qu)需要尺寸,切(qie)除多余(yu)(yu)電纜,套(tao)入熱縮三指套(tao)至三叉口(kou)根部(bu)由中間加熱收縮,由指套(tao)上(shang)口(kou)向(xiang)上(shang)量取(qu)規(gui)定尺寸(35kv為350~380mm)。去掉多余(yu)(yu)銅帶(dai)(保(bao)留20mm),再保(bao)留半導(dao)體預定位置,壓接(jie)出線(xian)端子密封。
30、電線(xian)電纜(lan)的(de)應用主要(yao)分為三(san)大類 :
(1)、電(dian)力系統(tong)
電(dian)力(li)系統采用的電(dian)線(xian)電(dian)纜產(chan)品主要有架(jia)空(kong)裸電(dian)線(xian)、匯流排(pai)(母(mu)線(xian))、電(dian)力(li)電(dian)纜(塑料線(xian)纜、油紙力(li)纜(基(ji)本被塑料電(dian)力(li)電(dian)纜代替)、橡套線(xian)纜、架(jia)空(kong)絕緣電(dian)纜)、分(fen)支電(dian)纜(取代部(bu)分(fen)母(mu)線(xian))、電(dian)磁線(xian)以及(ji)電(dian)力(li)設備用電(dian)氣裝備電(dian)線(xian)電(dian)纜等。
(2)、信息傳輸(shu)系統
用于信息傳輸(shu)系統(tong)的(de)電(dian)線(xian)電(dian)纜(lan)(lan)(lan)主要有市話電(dian)纜(lan)(lan)(lan)、電(dian)視電(dian)纜(lan)(lan)(lan)、電(dian)子線(xian)纜(lan)(lan)(lan)、射頻電(dian)纜(lan)(lan)(lan)、光纖纜(lan)(lan)(lan)、數據(ju)電(dian)纜(lan)(lan)(lan)、電(dian)磁線(xian)、電(dian)力通訊(xun)或(huo)其他復合電(dian)纜(lan)(lan)(lan)等。
(3)、機械設備、儀器儀表系統(tong)
此部分除(chu)架空(kong)裸電(dian)(dian)(dian)線(xian)(xian)外幾乎其他所有產品均有應用(yong),但主要是電(dian)(dian)(dian)力電(dian)(dian)(dian)纜、電(dian)(dian)(dian)磁線(xian)(xian)、數據電(dian)(dian)(dian)纜、儀(yi)器(qi)儀(yi)表(biao)線(xian)(xian)纜等(deng)。
31、電線電纜產品主(zhu)要(yao)分為五(wu)大(da)類:
(1)、裸(luo)電線(xian)及(ji)裸(luo)導(dao)體(ti)制品 本類產(chan)品的(de)主(zhu)(zhu)(zhu)要特征(zheng)是:純的(de)導(dao)體(ti)金屬,無絕緣及(ji)護套層,如(ru)鋼(gang)芯鋁絞線(xian)、銅鋁匯流排(pai)、電力(li)機車線(xian)等;加工工藝主(zhu)(zhu)(zhu)要是壓力(li)加工,如(ru)熔煉、壓延、拉制、絞合(he)(he)/緊壓絞合(he)(he)等;產(chan)品主(zhu)(zhu)(zhu)要用在城郊、農(nong)村、用戶主(zhu)(zhu)(zhu)線(xian)、開關柜等。
(2)、電(dian)(dian)(dian)力(li)電(dian)(dian)(dian)纜本類產品(pin)主(zhu)(zhu)要(yao)特征(zheng)是:在導體(ti)外擠(繞(rao))包絕緣層(ceng),如(ru)架空絕緣電(dian)(dian)(dian)纜,或幾芯(xin)絞合(對應電(dian)(dian)(dian)力(li)系統的相線(xian)、零線(xian)和地線(xian)),如(ru)二(er)芯(xin)以上架空絕緣電(dian)(dian)(dian)纜,或再增加護(hu)套層(ceng),如(ru)塑料/橡套電(dian)(dian)(dian)線(xian)電(dian)(dian)(dian)纜。主(zhu)(zhu)要(yao)的工(gong)藝(yi)技術有拉制、絞合、絕緣擠出(繞(rao)包)、成纜、鎧裝、護(hu)層(ceng)擠出等,各(ge)種(zhong)產品(pin)的不同工(gong)序組合有一定(ding)區別(bie)。
產品主要用在發、配、輸、變(bian)、供(gong)電線路(lu)中的強電電能(neng)傳輸,通過的電流大(幾十安至(zhi)幾千(qian)安)、電壓高(220V至(zhi)500kV及以上)。
(3)、電氣裝備(bei)用(yong)電線(xian)(xian)電纜(lan)(lan)(lan)該類(lei)產(chan)品主要特(te)(te)征是:品種規格繁(fan)多,應用(yong)范圍(wei)廣泛(fan),使用(yong)電壓在1kV及以下較多,面對特(te)(te)殊場合不斷衍生(sheng)新的(de)產(chan)品,如耐(nai)火(huo)線(xian)(xian)纜(lan)(lan)(lan)、阻燃(ran)線(xian)(xian)纜(lan)(lan)(lan)、低(di)煙(yan)無鹵(lu)/低(di)煙(yan)低(di)鹵(lu)線(xian)(xian)纜(lan)(lan)(lan)、防白蟻、防老鼠線(xian)(xian)纜(lan)(lan)(lan)、耐(nai)油/耐(nai)寒/耐(nai)溫/耐(nai)磨線(xian)(xian)纜(lan)(lan)(lan)、醫用(yong)/農用(yong)/礦(kuang)用(yong)線(xian)(xian)纜(lan)(lan)(lan)、薄(bo)壁電線(xian)(xian)等。
(4)、通訊(xun)(xun)電(dian)纜(lan)及光(guang)(guang)纖(簡略介紹)隨著近二十多年來,通訊(xun)(xun)行業的(de)(de)飛(fei)速(su)發展(zhan),產品(pin)也有驚人(ren)的(de)(de)發展(zhan)速(su)度(du)。從過去的(de)(de)簡單的(de)(de)電(dian)話電(dian)報(bao)線纜(lan)發展(zhan)到(dao)幾千對的(de)(de)話纜(lan)、同軸(zhou)纜(lan)、光(guang)(guang)纜(lan)、數據電(dian)纜(lan),甚至組合通訊(xun)(xun)纜(lan)等(deng)。
該類產品結構尺寸(cun)通常較(jiao)小(xiao)而均勻,制(zhi)造精度要求高。
(5)、電磁(ci)線(繞組線)主(zhu)要用于各(ge)種電機(ji)、儀器儀表等。
電線電纜的衍生/新產品
電線電纜的(de)衍生/新(xin)產品主要(yao)(yao)是因應用場合(he)、應用要(yao)(yao)求(qiu)(qiu)不同及(ji)裝備(bei)的(de)方便性和降低裝備(bei)成本等的(de)要(yao)(yao)求(qiu)(qiu),而采用新(xin)材(cai)(cai)料、特殊材(cai)(cai)料、或改變產品結構、或提高工藝(yi)要(yao)(yao)求(qiu)(qiu)、或將不同品種的(de)產品進(jin)行(xing)組合(he)而產生。
采用(yong)不同材(cai)料如阻燃線(xian)纜(lan)、低煙(yan)無鹵/低煙(yan)低鹵線(xian)纜(lan)、防白蟻、防老(lao)鼠線(xian)纜(lan)、耐油/耐寒/耐溫線(xian)纜(lan)等(deng);
改變產品結構如:耐火電纜(lan)等;
提高工藝要求如:醫用線(xian)纜等;
組合(he)產(chan)品如:OPGW等;
方便安裝和降低裝備成(cheng)本如:預制分支(zhi)電纜等。
32、母線裝(zhuang)置施工(gong)完,應進行哪些檢查?
答:應進行下列(lie)檢(jian)查:
(1)金屬構件的加工、配制、焊(han)接螺接應(ying)符合規(gui)定(ding);
(2)各部(bu)螺栓(shuan)、墊圈(quan)、開口(kou)銷等零部(bu)件應齊全可靠;
(3)母線配制及(ji)(ji)安裝架(jia)應(ying)符(fu)合規定(ding),相間及(ji)(ji)對地電氣距(ju)離符(fu)合要求;
(4)瓷(ci)件、鐵件及膠合處(chu)應(ying)完整(zheng),充油(you)套管應(ying)無滲(shen)油(you),油(you)位正常(chang);
(5)油(you)漆完整,相色正確,接地良(liang)好。
33、在35kv及(ji)以(yi)下電(dian)力電(dian)纜接(jie)頭(tou)中,改善其護(hu)套斷開處電(dian)場(chang)分布的方法有幾種(zhong)(請列出五種(zhong)),并簡(jian)述其方法。
答:(1)脹喇叭(ba)口:在鉛包(bao)割斷處把(ba)鉛包(bao)邊(bian)緣撬起,成喇叭(ba)狀,其邊(bian)緣應光滑、圓整、對稱。
(2)預(yu)留統包(bao)絕緣:在(zai)鉛包(bao)切(qie)口(kou)至電纜芯線(xian)分開點之間(jian)留有一段統包(bao)絕緣紙(zhi)。
(3)切除半(ban)導電(dian)紙(zhi)(zhi):將(jiang)半(ban)導電(dian)紙(zhi)(zhi)切除到喇叭口(kou)以下。
(4)包繞應力錐:用(yong)絕(jue)緣包帶和導電金屬材料(liao)包成(cheng)錐形,人為地將屏(ping)蔽層擴大,以改善電場分布。
(5)等電位法:對于干包型或交聯聚乙烯電纜(lan)頭,在各線芯概況絕緣表面上包一段金(jin)屬帶,并將其連接在一起。
(6)裝(zhuang)設(she)應力(li)(li)控制管:對于35kv及發(fa)下熱縮管電(dian)纜頭,首(shou)先從線(xian)芯(xin)銅屏蔽(bi)層(ceng)末(mo)端方向經半導體帶(dai)至線(xian)芯(xin)絕(jue)緣概況(kuang)包繞2層(ceng)半導體帶(dai),然后(hou)將相應規格折應力(li)(li)管,套(tao)在銅屏蔽(bi)的末(mo)端處,熱縮成形。
34、電纜支架的加(jia)工應(ying)符合哪(na)些(xie)要求(qiu)?
答:(1)鋼材應(ying)平(ping)直(zhi),無明顯扭曲,下料誤差應(ying)在5mm范圍內(nei),切口應(ying)無卷邊(bian),毛剌;
(2)支架(jia)應焊接牢固(gu),無(wu)顯蓍變形,各橫撐(cheng)間的垂直(zhi)凈距與設計偏(pian)差不(bu)應大于5mm;
(3)金屬支架必須進行防腐(fu)處理(li),位于濕熱、鹽、霧以及(ji)有化(hua)學(xue)腐(fu)蝕(shi)地區時,應根據設計作特殊的防腐(fu)處理(li)。
35、列舉(ju)出你(ni)熟悉的電纜架(jia)。
答:拼焊式E型架(jia)、裝配式E型架(jia)、橋式電纜(lan)架(jia)、電纜(lan)托架(jia)、掛鉤式支架(jia)、單(dan)根電纜(lan)支架(jia)等。
36、敷設(she)電纜應滿足哪些要求(qiu)?
答(da):應滿足以下要求:
(1)安全(quan)運行(xing)方面,盡可能(neng)避免各種外來損(sun)壞,提高電纜(lan)線路的供(gong)電可靠性;
(2)經濟方面(mian),從投資最省的方面(mian)考慮(lv);
(3)施工(gong)方面,電纜線路的路徑必須便于旋工(gong)和投(tou)運后的維修。
37、制作電纜終端頭或中間接頭的絕緣(yuan)材料有哪些?
答:有(you)絕(jue)緣(yuan)膠、絕(jue)緣(yuan)帶、絕(jue)緣(yuan)管、絕(jue)緣(yuan)手套、絕(jue)緣(yuan)樹脂等。
38、簡述電(dian)纜頭制(zhi)(zhi)作的一般操作程序(xu)。答:(1)制(zhi)(zhi)作前(qian)的準備(bei):包括○1閱讀安(an)裝(zhuang)說明書(shu);○2察看現場;○3備(bei)料;○4電(dian)纜試(shi)潮(chao);○5制(zhi)(zhi)作前(qian)測試(shi)等。
(2)接(jie)頭的制(zhi)作過程(cheng):包括○1割斷多余電(dian)纜(lan);○2電(dian)纜(lan)保護層的剝(bo)切(qie);○3導(dao)體連接(jie);○4包繞(rao)絕緣(或收縮管(guan)材);○5安裝接(jie)頭外(wai)殼;○6灌注絕緣劑;○7進行密封處理等。
(3)制作后電氣測試。
39、電纜保(bao)護管的(de)加工應符合哪(na)些(xie)要求?
答:(1)管口(kou)應*剌和尖(jian)銳楞角,管口(kou)宜做成喇(la)叭形。
(2)電(dian)纜(lan)管在彎(wan)制后,不應有裂縫和顯著的凹癟現(xian)象(xiang),其(qi)彎(wan)扁程(cheng)度(du)不宜大于(yu)管子外徑10%;電(dian)纜(lan)管的彎(wan)曲半徑不應小于(yu)所穿入電(dian)纜(lan)的最小允許彎(wan)曲半徑。
(3)金屬管應(ying)在外表涂防(fang)腐(fu)漆(qi)(qi)或瀝(li)表,鍍鋅管鋅層剝(bo)落(luo)處也應(ying)涂以防(fang)腐(fu)漆(qi)(qi)。
40、電(dian)纜的排列符合哪些要求?答:(1)電(dian)力(li)電(dian)纜和控纜不應(ying)配置在同一層支(zhi)架上(shang)。
(2)高、低壓電(dian)纜,強、弱(ruo)電(dian)控纜應按須序分(fen)層配置(zhi),一般情況宜由(you)上而(er)下,但(dan)在含有(you)35kv以(yi)上高壓電(dian)纜引入(ru)柜盤時(shi),為滿足彎(wan)曲(qu)半(ban)徑,可由(you)下面上配置(zhi)。
41、電纜(lan)溝內敷設(she)電纜(lan)的方法是(shi)什(shen)么?
答:在電(dian)(dian)纜(lan)(lan)(lan)溝內敷(fu)設(she)電(dian)(dian)纜(lan)(lan)(lan)的方法(fa)與(yu)直埋電(dian)(dian)纜(lan)(lan)(lan)的敷(fu)設(she)方法(fa)相仿,一(yi)般可將(jiang)滑輪放(fang)在溝內,施(shi)放(fang)完(wan)畢,將(jiang)電(dian)(dian)纜(lan)(lan)(lan)放(fang)于溝底或支(zhi)架上,并在電(dian)(dian)纜(lan)(lan)(lan)上綁扎電(dian)(dian)纜(lan)(lan)(lan)標牌。
42、電纜敷設的常用設備有哪些?
答:(1)空(kong)氣壓縮機,主要用(yong)來破壞路面,為以后敷設(she)電(dian)纜作準備;
(2)電動卷揚機或(huo)電纜(lan)牽(qian)引機,主要(yao)用來拖(tuo)電纜(lan);
(3)電纜輸送機,配合牽(qian)引機使用來(lai)克服(fu)巨(ju)大的摩擦力,減輕對電纜的損壞;
(4)電纜盤(pan)放線支架;
(5)滾(gun)輪裝置;
(6)防捻 ,減鋼(gang)絲(si)繩出現的(de)扭曲;
(7)電(dian)纜盤制動裝置;
(8)張力計。
43、電(dian)(dian)(dian)纜溝(gou)中支架(jia)安裝距離的要求如(ru)何(he)?答:電(dian)(dian)(dian)纜固定于(yu)(yu)電(dian)(dian)(dian)纜溝(gou)和隧(sui)道的墻上,水平裝置(zhi)時(shi),當電(dian)(dian)(dian)纜外(wai)徑(jing)(jing)等于(yu)(yu)或小于(yu)(yu)50mm時(shi)應每(mei)(mei)隔1m加一支撐;外(wai)徑(jing)(jing)大于(yu)(yu)50mm的電(dian)(dian)(dian)纜每(mei)(mei)隔0.6m加一支撐;排(pai)成三角形的單(dan)電(dian)(dian)(dian)纜,每(mei)(mei)隔1m應用綁帶扎(zha)牢,垂直裝置(zhi)時(shi),每(mei)(mei)隔1~1.5m加以(yi)固定。
44、如何處理電力電纜(lan)與控制電纜(lan)在同(tong)一托架的安裝?
答:電(dian)(dian)力電(dian)(dian)纜(lan)與(yu)控制電(dian)(dian)纜(lan)一(yi)(yi)般不(bu)應(ying)敷(fu)(fu)設(she)在(zai)同一(yi)(yi)托架(jia)內(nei),當電(dian)(dian)纜(lan)較少而將控纜(lan)與(yu)電(dian)(dian)力電(dian)(dian)纜(lan)敷(fu)(fu)設(she)在(zai)同一(yi)(yi)托架(jia)內(nei)時,應(ying)用隔(ge)板隔(ge)開。
45、電纜隧道內如何裝設(she)接地(di)線?
答:隧道和溝的全長應(ying)裝(zhuang)設連續的接(jie)(jie)(jie)地(di)(di)線(xian)(xian)(xian),接(jie)(jie)(jie)地(di)(di)線(xian)(xian)(xian)應(ying)和所有的支(zhi)架相(xiang)連,兩頭和接(jie)(jie)(jie)地(di)(di)極連通。接(jie)(jie)(jie)地(di)(di)線(xian)(xian)(xian)的規格應(ying)符合設計要求。電(dian)纜鉛包和鎧(kai)裝(zhuang)除了有絕(jue)緣(yuan)要求外,應(ying)全部相(xiang)互連接(jie)(jie)(jie)并(bing)和接(jie)(jie)(jie)地(di)(di)線(xian)(xian)(xian)相(xiang)連,電(dian)纜架和接(jie)(jie)(jie)地(di)(di)線(xian)(xian)(xian)均應(ying)涂防(fang)銹漆或鍍鋅。
46、對于電纜孔洞的(de)防火封堵有何(he)要求?
答:對于較大的電纜(lan)(lan)貫穿孔(kong)(kong)洞,如電纜(lan)(lan)貫穿樓板處(chu)等,采(cai)用防火堵(du)料(liao)封(feng)(feng)堵(du)時(shi),應根據實(shi)際情況(kuang),先在電纜(lan)(lan)表面涂(tu)四至六層防火涂(tu)料(liao),長度(du)自孔(kong)(kong)洞以(yi)下(xia)1.5m左右,再用耐(nai)火材料(liao)加(jia)工(gong)成具(ju)有(you)(you)一定(ding)強度(du)的板托防火堵(du)料(liao),保(bao)證封(feng)(feng)堵(du)后牢(lao)固并(bing)便于更換(huan)電纜(lan)(lan)時(shi)拆裝,封(feng)(feng)堵(du)密實(shi)無孔(kong)(kong)隙以(yi)有(you)(you)效地堵(du)煙堵(du)火。
47、噴燈點火前應注意哪些檢查?
答:應進行下列各項檢查:
(1)打(da)氣筒(tong)是否漏油或滲油,油桶及噴嘴(zui)處是否漏油、漏氣;
(2)油桶(tong)(tong)內的(de)油量(liang)是(shi)否超(chao)過油桶(tong)(tong)容量(liang)的(de)3/4,加油的(de)螺絲塞(sai)是(shi)否擰緊。
48、使(shi)用噴燈應(ying)注(zhu)意哪些事項(xiang)?
答:(1)噴(pen)燈更大 注油量為(wei)油筒(tong)容積的3/4;
(2)開(kai)始(shi)打氣壓力不要太大,點燃后火焰由黃變藍(lan)即可使用;
(3)周圍(wei)不(bu)得(de)有易燃物,空(kong)氣要流通;
(4)停用時先(xian)關閉調(diao)節(jie)開關,火熄后,慢慢旋松(song)油孔(kong)蓋放氣,空氣放完(wan)后,要(yao)要(yao)旋松(song)調(diao)節(jie)開關,完(wan)全(quan)冷卻后再旋松(song)孔(kong)蓋;
(5)煤油(you)噴(pen)燈與汽油(you)噴(pen)燈要分開使用(yong)。
49、手動油壓鉗(qian)有何用途?如何操(cao)作?
答:兩(liang)根導(dao)線的連接(jie)(jie)通常是將兩(liang)導(dao)線端穿(chuan)入(ru)相同材料(liao)制(zhi)成的壓(ya)(ya)(ya)管中,用(yong)壓(ya)(ya)(ya)接(jie)(jie)鉗擠(ji)壓(ya)(ya)(ya)數個(ge)(ge)坑(keng),使導(dao)線連接(jie)(jie)在一起,壓(ya)(ya)(ya)接(jie)(jie)時,手柄向上抬起時,柱(zhu)(zhu)塞向外移(yi)(yi)動(dong),進(jin)油(you)(you)閥(fa)下(xia)腔(qiang)產(chan)生真空(kong),油(you)(you)箱(xiang)內的油(you)(you)進(jin)入(ru)柱(zhu)(zhu)塞腔(qiang)。手柄下(xia)壓(ya)(ya)(ya)時,柱(zhu)(zhu)塞向內移(yi)(yi)動(dong),油(you)(you)受壓(ya)(ya)(ya)后(hou),使進(jin)油(you)(you)閥(fa)關(guan)閉,打(da)開(kai)出油(you)(you)閥(fa),使油(you)(you)壓(ya)(ya)(ya)進(jin)入(ru)液(ye)壓(ya)(ya)(ya)缸(gang),推動(dong)活塞和(he)陽(yang)模(mo),陽(yang)、陰模(mo)之間放有(you)壓(ya)(ya)(ya)接(jie)(jie)管,當壓(ya)(ya)(ya)接(jie)(jie)被擠(ji)壓(ya)(ya)(ya)的坑(keng)深到一定值時,開(kai)啟回油(you)(you)閥(fa),活塞自動(dong)返回,壓(ya)(ya)(ya)完(wan)一個(ge)(ge)坑(keng)后(hou),移(yi)(yi)動(dong)壓(ya)(ya)(ya)鉗,再壓(ya)(ya)(ya)下(xia)一個(ge)(ge)。
50、常用低壓(ya)電力電纜按絕緣和保(bao)護層的不同,主要可分為哪幾類?
答:(1)油浸紙絕(jue)緣鉛包(bao)(或(huo)鋁包(bao))電(dian)力電(dian)纜;
(2)不(bu)滴流(liu)油浸(jin)紙(zhi)絕緣電(dian)(dian)力電(dian)(dian)纜(lan);
(3)聚(ju)氯乙(yi)烯絕緣聚(ju)氯乙(yi)烯護套電(dian)力電(dian)纜(lan);
(4)交聯聚氯乙(yi)(yi)烯(xi)絕緣(yuan)聚乙(yi)(yi)烯(xi)護套電力電纜;
(5)交聯聚(ju)氯乙烯絕緣聚(ju)氯乙烯護(hu)套(tao)電(dian)力電(dian)纜;
(6)橡皮絕(jue)緣電(dian)(dian)力電(dian)(dian)纜。
51、常用(yong)絕緣(yuan)材料的類別哪些?舉例說(shuo)明?
答:(1)無機(ji)絕(jue)緣材料(liao):有云母、石棉(mian)、大理石、瓷器、玻璃(li)等;
(2)有(you)機(ji)絕緣材料:有(you)樹脂、橡(xiang)膠、紙、麻(ma)、棉紗等;
(3)混合絕緣材料(liao):用以(yi)上絕緣材料(liao)加工而(er)成型的名種絕緣材料(liao)。
52、在哪種情況(kuang)下采用排管敷設?有什么優(you)點?
答:排管敷設一(yi)般用(yong)在(zai)與(yu)其他建(jian)筑物、公路或鐵(tie)路相交(jiao)叉的地方,有時也在(zai)建(jian)筑物密集區(qu)內采用(yong)。主要(yao)優點是占地少,能承受(shou)大的荷重,電纜相互(hu)(hu)間(jian)互(hu)(hu)不影(ying)響,比較安全。
53、何謂電纜長期允許載流量?
答:電纜(lan)長(chang)期(qi)允許載流量(liang)是指在電纜(lan)內通過規定(ding)(ding)電流時,在熱穩定(ding)(ding)后,電纜(lan)導體達到長(chang)期(qi)允許工作溫(wen)度時的電流數值。
54、決定電纜長期允許載(zai)流量的因(yin)素有哪些?
答:有以下三個因素決定:
(1)電(dian)纜的長(chang)期容(rong)許工作(zuo)溫度;
(2)電纜本身的散(san)熱(re)性能(neng);
(3)電纜裝置情況及周圍環境的(de)散熱條件。
55、電纜(lan)的敷(fu)設方式有幾種?
答:有(you)以下幾種:
(1)直埋在地下;
(2)安裝(zhuang)在電纜溝內;
(3)安裝在(zai)地下隧道內(nei);
(4)安裝(zhuang)在建筑物內部墻上(shang)(shang)或天棚上(shang)(shang);
(5)安(an)裝在(zai)橋架上;
(6)敷設(she)在(zai)排管內;
(7)敷設在水底。
56、如(ru)何(he)進(jin)行電(dian)纜管的連(lian)接工作?
答:電纜管(guan)連(lian)接(jie)(jie)時,必須用扣和管(guan)接(jie)(jie)頭連(lian)接(jie)(jie),如(ru)采用焊接(jie)(jie)時,不能直接(jie)(jie)對(dui)焊,連(lian)接(jie)(jie)處要套(tao)上一段粗管(guan)再進行(xing)焊接(jie)(jie),以(yi)免焊渣(zha)掉入管(guan)內。
57、制作電(dian)纜(lan)頭時,對上下扳彎電(dian)纜(lan)芯線有何要求?
答:扳彎線(xian)(xian)芯(xin)時,不得(de)損(sun)(sun)傷(shang)紙絕(jue)(jue)緣,芯(xin)線(xian)(xian)的(de)彎曲半徑不得(de)小于(yu)電(dian)纜線(xian)(xian)芯(xin)的(de)10倍。制(zhi)作時要特(te)別小心,應使線(xian)(xian)芯(xin)彎曲部(bu)分均(jun)勻受力,否則極易(yi)損(sun)(sun)傷(shang)絕(jue)(jue)緣紙。
58、簡(jian)述(shu)塑(su)料電(dian)纜(lan)的(de)熱(re)收縮密封(feng)法(fa)。
答:熱(re)(re)(re)縮(suo)法適用于中、低壓橡、塑(su)電(dian)纜接頭(tou)(tou)和(he)終端(duan)頭(tou)(tou)的密封(feng)(feng)(feng),也可(ke)適用于不滴(di)流和(he)黏性(xing)浸漬絕緣電(dian)纜。采用交聯聚(ju)乙烯型(xing)和(he)硅(gui)橡膠(jiao)型(xing)兩大類遇熱(re)(re)(re)后(hou)能(neng)均勻收縮(suo)的熱(re)(re)(re)收縮(suo)管。將(jiang)這種管材套于預定的粘合密封(feng)(feng)(feng)部位(wei),并在粘和(he)部位(wei)涂上熱(re)(re)(re)熔膠(jiao),當加熱(re)(re)(re)到一定溫(wen)度后(hou),熱(re)(re)(re)縮(suo)管將(jiang)收縮(suo),同時熱(re)(re)(re)熔膠(jiao)熔化,待自然冷卻后(hou)即形(xing)成一道(dao)良好的密封(feng)(feng)(feng)封(feng)(feng)(feng)層。
59、用電(dian)(dian)動彎管(guan)機彎制電(dian)(dian)纜(lan)保護管(guan)時應注意(yi)什(shen)么?
答(da):(1)彎管機(ji)應由了解其性能并熟悉操作知識的人員操作;
(2)使用前必(bi)須進行檢查,按鈕、操作把手、行程(cheng)開關應完好,彎管機必(bi)須可(ke)靠接地;
(3)選用符(fu)合要求的(de)模具,確定好所需要的(de)彎曲(qu)半徑;
(4)施(shi)工場地周圍,應有(you)充足的(de)活動(dong)范圍;
(5)使用時待空轉(zhuan)正常(chang)后,方(fang)可帶負(fu)荷(he)工作,運行中,嚴禁用手腳接觸其(qi)轉(zhuan)動部(bu)分(fen);
(6)工作(zuo)完畢(bi)應及時停電,釋放油壓。
60、電纜清冊的內(nei)容(rong)及電纜編號的含義(yi)是(shi)什(shen)么?
答:電纜清冊是施放電纜和指(zhi)導(dao)施工的(de)依據(ju),運(yun)行維護的(de)檔案資料。應(ying)列入每(mei)根電纜的(de)編(bian)號、起始點(dian)、型號、規格、長(chang)度,并分類統計出總長(chang)度,控纜還應(ying)列出每(mei)根電纜的(de)備用芯。
電纜編號是(shi)識別電纜的標志,故(gu)要求(qiu)全廠編號不重復(fu),并且有一定(ding)的含義和(he)規律,能表(biao)達(da)電纜的特征。
61、電纜目(mu)前采用的(de)敷設方(fang)法可分為幾類?
答(da):(1)人(ren)工敷設,即采用人(ren)海戰術(shu),在一人(ren)或多人(ren)協調指揮下,按規定進行敷設;
(2)機械(xie)化敷設,即(ji)采用(yong)滾輪、牽(qian)引器、輸送機,通過一同步電源(yuan)進行控制,比較安全;
(3)人工(gong)和機械相結合,有些現場由于轉彎(wan)較多,施工(gong)難度大,全用(yong)機械較困(kun)難,所以采用(yong)此法。
62、控制二次回路(lu)接線應符合哪些要求(qiu)?
答:(1)按(an)圖施工接線正確;
(2)導線的(de)電氣連接應(ying)牢(lao)固可(ke)靠;
(3)盤柜內的導線不應(ying)有接頭(tou),導線芯(xin)線應(ying)無損傷(shang);
(4)電纜(lan)芯線端部(bu)應(ying)(ying)標明其(qi)回路編號,編號應(ying)(ying)正確(que),字跡清晰且不易脫(tuo)色;
(5)配線應整齊(qi)、清晰、美觀,導線絕緣應良好、無損;
(6)每(mei)個接線端子的每(mei)側(ce)接線宜為一根,最多不(bu)得超過兩(liang)根。
63、電(dian)纜(lan)排管有(you)何要求?
答:(1)排管頂部至(zhi)地(di)面距(ju)離,在廠(chang)房(fang)內為0.2m,人行道下為0.5m,一般(ban)地(di)區為0.7m;
(2)在(zai)變(bian)更方向及分支(zhi)處均應裝(zhuang)置排管井坑(keng),長度超(chao)過30mm時也應加設井坑(keng);
(3)井坑深度不小(xiao)于0.8m,人孔直(zhi)徑不小(xiao)于0.7mm;
(4)排(pai)管(guan)應有傾向井坑0.5%~1%的(de)排(pai)水坡度。
64、對于電纜(lan)導(dao)體連(lian)接點的電阻有何要求(qiu)?
答(da):要求連(lian)接點(dian)的(de)(de)電阻小而且穩定,連(lian)接點(dian)的(de)(de)電阻與相同(tong)(tong)長度、相同(tong)(tong)截(jie)面的(de)(de)導體之比(bi)值,對(dui)于(yu)(yu)新安裝的(de)(de)終端(duan)頭和(he)中間頭,應不大(da)于(yu)(yu)1;對(dui)于(yu)(yu)運行中的(de)(de)終端(duan)頭和(he)中間頭這個比(bi)值不應大(da)于(yu)(yu)1.2。
65、電纜接頭(tou)和(he)中間頭(tou)的設計(ji)應滿足哪些要求?
答:應滿足的要求有:
(1)耐壓(ya)強度(du)高,導體連接好;
(2)機械強度大,介質損失小;
(3)結構簡單,密封性強。
66、什(shen)么是電纜故障(zhang)?有幾種(zhong)常見(jian)的類型?
答:電(dian)纜故障(zhang)(zhang)(zhang)是指電(dian)纜在預防性試驗時發生絕緣擊穿或在運行中,因絕緣擊穿、導(dao)線燒斷等而迫使(shi)電(dian)纜線路停電(dian)的故障(zhang)(zhang)(zhang)。常見的故障(zhang)(zhang)(zhang)有接地故障(zhang)(zhang)(zhang)、短路故障(zhang)(zhang)(zhang)、斷線故障(zhang)(zhang)(zhang)、閃(shan)絡性故障(zhang)(zhang)(zhang)和混合型故障(zhang)(zhang)(zhang)等。
67、如何處理電(dian)纜線路的單(dan)相接地故障(zhang)?
答(da):電(dian)(dian)纜(lan)線路(lu)單相接地故障一(yi)(yi)(yi)般來(lai)說(shuo),電(dian)(dian)纜(lan)導體的(de)(de)(de)損傷只(zhi)是局(ju)部的(de)(de)(de),如果屬(shu)于機械損傷,而故障點附(fu)近的(de)(de)(de)土(tu)壤又較(jiao)干燥時,一(yi)(yi)(yi)般可進行局(ju)部修(xiu)理,加添一(yi)(yi)(yi)只(zhi)假接頭,即(ji)不將電(dian)(dian)纜(lan)芯鋸(ju)斷,僅將故障點絕(jue)緣加強后密封即(ji)可。
68、電力(li)電纜在敷設(she)前應進(jin)行(xing)哪些試驗和(he)檢查(cha)?
答:敷設前應檢查(cha)電纜的型(xing)號、規格及長度(du)是否符合要(yao)求,是否有外(wai)力(li)損傷,低壓電纜用1000V兆歐表(biao)遙測絕緣電阻,阻值(zhi)一般不低于10MΩ,高壓電纜用2500V兆歐表(biao)搖測阻值(zhi)一般不抵(di)于400MΩ。
69、主(zhu)廠房內(nei)敷設電(dian)纜時一般應注意什么?
答:在主廠房內敷設電纜時一般應注意:
(1)凡引至集控室的(de)控制電纜宜架空敷設(she);
(2)6KV電(dian)纜(lan)宜用隧道或(huo)排管敷設(she),地下水位高處(chu)亦可架(jia)空或(huo)用排管敷設(she);
(3)380V電纜(lan)當兩端電纜(lan)在零米時宜用隧道、溝或排管,當一端設(she)備在上、一端在下時,可(ke)部分架(jia)空敷設(she),當地下水位較高時,宜架(jia)空。
70、電(dian)(dian)力(li)電(dian)(dian)纜的(de)內屏蔽(bi)層(ceng)與外屏蔽(bi)層(ceng)各在什(shen)(shen)么部位(wei)?采用(yong)什(shen)(shen)么材(cai)料?有(you)何作用(yong)?
答:為(wei)了使(shi)絕(jue)緣(yuan)層(ceng)(ceng)和(he)電(dian)纜導(dao)體(ti)有較(jiao)好的(de)(de)接觸,消除導(dao)體(ti)表面(mian)的(de)(de)不光滑引起的(de)(de)導(dao)體(ti)表面(mian)電(dian)場強度的(de)(de)增(zeng)加,一(yi)般在(zai)導(dao)體(ti)表面(mian)包(bao)有金(jin)屬化紙或半導(dao)體(ti)紙帶的(de)(de)內(nei)屏蔽層(ceng)(ceng)。為(wei)了使(shi)絕(jue)緣(yuan)層(ceng)(ceng)和(he)金(jin)屬護(hu)套(tao)有較(jiao)好的(de)(de)接觸,一(yi)般在(zai)絕(jue)緣(yuan)層(ceng)(ceng)外(wai)表面(mian)包(bao)有外(wai)層(ceng)(ceng)屏蔽層(ceng)(ceng)。外(wai)屏層(ceng)(ceng)與內(nei)屏層(ceng)(ceng)的(de)(de)材料相同,有時還外(wai)扎銅帶或編織銅絲帶。
71、簡述環氧(yang)樹脂(zhi)復合物(wu)的構成(cheng)及性能。
答:環(huan)氧樹(shu)脂復合物由環(huan)氧樹(shu)脂加(jia)入(ru)硬化劑(ji)(ji)、填(tian)充劑(ji)(ji)增韌(ren)劑(ji)(ji)和稀釋劑(ji)(ji)組成。具有以(yi)下性(xing)能:
(1)有足(zu)夠(gou)的機械(xie)強(qiang)度;
(2)電氣(qi)性能優(you)良;
(3)電氣性能穩定;
(4)與(yu)有(you)色金屬有(you)足夠的黏附力(li);
(5)耐(nai)腐(fu)蝕性好(hao);
(6)戶外使用時,耐(nai)雨、耐(nai)光、耐(nai)濕熱。
72、單芯(xin)電纜(lan)護(hu)套一端接地(di)方(fang)式中為(wei)什么必須(xu)安裝一條沿電纜(lan)平行敷(fu)設的回流線?
答:在金(jin)屬護套(tao)一(yi)端(duan)接(jie)地(di)(di)的(de)電(dian)(dian)(dian)纜線(xian)(xian)路(lu)中(zhong),為確(que)保護套(tao)中(zhong)的(de)感應電(dian)(dian)(dian)壓(ya)(ya)不超過(guo)(guo)允許標準(zhun),必須安(an)裝一(yi)條沿(yan)電(dian)(dian)(dian)纜線(xian)(xian)路(lu)平(ping)行(xing)敷設的(de)導(dao)體,且導(dao)體的(de)兩端(duan)接(jie)地(di)(di),這種導(dao)體稱為回(hui)流(liu)(liu)線(xian)(xian)。當發生單相接(jie)地(di)(di)故障時,接(jie)地(di)(di)短(duan)路(lu)電(dian)(dian)(dian)流(liu)(liu)可以通(tong)過(guo)(guo)回(hui)流(liu)(liu)線(xian)(xian)流(liu)(liu)回(hui)系統中(zhong)心點,由于通(tong)過(guo)(guo)回(hui)流(liu)(liu)線(xian)(xian)的(de)接(jie)地(di)(di)電(dian)(dian)(dian)流(liu)(liu)產生的(de)磁通(tong)抵消了一(yi)部分(fen)電(dian)(dian)(dian)纜導(dao)線(xian)(xian)接(jie)地(di)(di)電(dian)(dian)(dian)流(liu)(liu)所(suo)產生的(de)磁通(tong),因而可降(jiang)低短(duan)路(lu)故障時護套(tao)的(de)感應電(dian)(dian)(dian)壓(ya)(ya)。
73、電纜工程可劃分(fen)為幾(ji)個項目?
答(da):(1)工地運輸:包括(kuo)工程(cheng)(cheng)材料從(cong)倉庫(ku)到施(shi)工點的裝卸、運輸和空車回程(cheng)(cheng)。
(2)地(di)方工(gong)程:包括路(lu)面(mian)開挖、隧、溝道施工(gong)等。
(3)敷(fu)設工程:包(bao)括敷(fu)設、中間頭(tou)制(zhi)作、掀蓋板、埋(mai)管(guan)、校潮、牽(qian)引頭(tou)制(zhi)作等。
(4)兩端(duan)工程(cheng):包括支(zhi)、吊橋架(jia)和其基礎的(de)制作(zuo)安裝(zhuang),終端(duan)頭(tou)制作(zuo),油(you)壓力(li)和信號裝(zhuang)置的(de)安裝(zhuang),名(ming)種電氣性能測試(shi)等(deng)。
(5)塞(sai)止(zhi)工(gong)程(cheng):包括充油電(dian)纜塞(sai)止(zhi)頭制作,供油箱、自動排水及信號裝置的(de)安裝等。
(6)接地工程:包(bao)括(kuo)絕緣接頭、換位箱(xiang)、保(bao)護器、接地箱(xiang)安裝等。
74、電纜線路的(de)驗收(shou)應(ying)進行哪些檢查?
答:(1)電纜(lan)規(gui)格應符(fu)合規(gui)定,排列應整(zheng)齊,無損傷,標牌齊全(quan)、正確、清晰(xi);
(2)電(dian)纜的固定彎曲(qu)半徑、有關距(ju)離及單芯電(dian)力電(dian)纜的金屬護(hu)層的接線應符(fu)合要求;
(3)電纜終端、中間(jian)頭不(bu)滲漏油,安裝牢固,充(chong)油電纜油壓及表計整定值應符合(he)要求;
(4)接地良好(hao);
(5)電纜終(zhong)端相(xiang)色正確(que),支架等的金屬部件(jian)油漆(qi)完整;
(6)電纜溝(gou)及隧道內(nei)、橋架上(shang)應(ying)無雜物,蓋板齊(qi)全。
75、電纜線(xian)路正(zheng)序阻(zu)抗測量過程中有什么要求?
答:電(dian)纜導體的交流電(dian)阻和電(dian)纜三相同感抗的相量和稱為正序阻抗。
電纜線路的(de)正(zheng)序阻抗一(yi)般可在(zai)電纜盤上(shang)(shang)直接測(ce)量,測(ce)量時一(yi)般使用(yong)較低的(de)電壓,因此,需要用(yong)降(jiang)壓變壓器進行降(jiang)壓,降(jiang)壓器采用(yong)星形接線,容量一(yi)般為10kVA以上(shang)(shang),有較廣的(de)電壓調節范圍,測(ce)量時交流(liu)電源應比較穩(wen)定,以保證測(ce)量時電流(liu)達(da)到規(gui)定的(de)要求,實際電壓表的(de)讀(du)數值(zhi)必須是(shi)電纜端的(de)電壓,試(shi)驗(yan)電流(liu)更好(hao) 接近電纜長期允許(xu)載流(liu)量,測(ce)讀(du)各表計的(de)數值(zhi)時,合(he)上(shang)(shang)電流(liu)后同(tong)時讀(du)取(qu)三個表的(de)數值(zhi)。
76、根據《電業生產(chan)安全規(gui)定》,電氣工作人員必須具備(bei)的條件是(shi)什(shen)么(me)?
答:必須具備下(xia)列條件:
(1)經醫生鑒定(ding)身體健康,無妨礙工作的病癥;
(2)具備必要的(de)電氣(qi)知(zhi)識,按(an)其(qi)職務(wu)和(he)工作性質(zhi)掌握相關的(de)規程、專業技術及安全操作技術,并經考試合格;
(3)熟練(lian)掌握觸電急救方法(fa)。
77、電纜在運輸(shu)裝卸(xie)過程中應(ying)注(zhu)意(yi)什么?
答:(1)在運輸裝卸過程中,不(bu)應(ying)使電(dian)纜及電(dian)纜盤受到損傷,嚴禁將電(dian)纜盤直接(jie)由車上推(tui)下,電(dian)纜般不(bu)應(ying)平(ping)放運輸,平(ping)放貯存。
(2)運輸或滾動電(dian)纜(lan)(lan)盤(pan)前,必須保(bao)證電(dian)纜(lan)(lan)盤(pan)牢固,電(dian)纜(lan)(lan)繞緊、充油(you)(you)電(dian)纜(lan)(lan)至壓力(li)油(you)(you)箱(xiang)間的油(you)(you)管應(ying)固定,不得損(sun)傷,壓力(li)油(you)(you)箱(xiang)應(ying)牢固,壓力(li)指(zhi)示應(ying)符(fu)合要(yao)求。
78、電纜防火(huo)有哪些措施?
答:(1)采用阻燃電纜;
(2)采用防火(huo)電(dian)纜托(tuo)架;
(3)采(cai)用防火涂料(liao);
(4)電纜隧道(dao)、夾層出口等處設置防火隔墻、防火擋板;
(5)架空電纜應(ying)避開油管道、防(fang)(fang)爆門,否則應(ying)有要取局部穿管或隔(ge)熱防(fang)(fang)火措施。
79、選擇(ze)電(dian)力電(dian)纜的截面應從哪(na)幾個方面考慮?
答:應(ying)考慮如(ru)下幾個方面:
(1)電纜長期允(yun)許通過的工作電流(liu);
(2)一旦短路時的熱穩定性;
(3)線(xian)路上的電壓降(jiang)不能超出允許工(gong)作范圍(wei)。
80、電力(li)電纜和架空線比較有哪些(xie)優點?
答(da):(1)運行可靠,由于安(an)裝在地下(xia)等隱蔽處,受(shou)外(wai)力破壞小,發生故障(zhang)的機會(hui)較少,供電安(an)全(quan),不會(hui)給人身造(zao)成危害(hai);
(2)維護工作量(liang)小(xiao),不(bu)需(xu)頻繁的巡檢;
(3)不需(xu)架設(she)桿(gan)塔;
(4)有(you)助于(yu)提高功率因(yin)數。